Page 823 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 823

ABB  MOTOR PROTECTION AND CONTROL                                                 9/3

          —

          S800S-SCL-SR/S803W-SCL-SR
          Technical data





                                            S800S-SCL-SR                      S803W-SCL-SR
          Rated operational current Ie    [A] 32, 63, 100                     32, 63, 100
          Pole                              1, 2, 3                           3
          Rated operational voltage Ue   50/60 Hz  [V] 400/690                690
          (AC) according to IEC 60947-2
          (AC) according to UL 508   50/60 Hz  [V]                            600
          Rated insulation voltage Ui     [V] 690                             690
          Rated impulse withstand voltage Uimp   [kV] 8                       8
          Rated ultimate short-circuit breaking capacity
          Icu = Ics according to IEC 60947-2 *
          (AC) 50/60 Hz 240/415 V        [kA] 100                             100
          (AC) 50/60 Hz 254/440 V        [kA] 100                             100
          (AC) 50/60 Hz 277/480 V        [kA] 65                              65
          (AC) 50/60 Hz 289/500 V        [kA] 65                              65
          (AC) 50/60 Hz 346/600 V        [kA] 65                              65
          (AC) 50/60 Hz 400/690 V        [kA] 50                              50
          Short-circuit rating according to UL 508, CSA 22.2 *
          (AC) 50/60 Hz 480 V            [kA] 65                              65
          (AC) 50/60 Hz 600 V            [kA] 65                              65
          *  Valid only for approved combinations
          Rated frequency                [Hz] 50/60                           50/60
          Mounting position                 any                               any
          Connections Cu
                                        [mm²] 1 … 50 rigid (solid/stranded)   1 … 50 rigid (solid/stranded)
                                        [mm²] 1 … 70 flexible                 1 … 70 flexible
                                                                              14–1 AWG
          Tightening torque
                                         [Nm] min. 3 / max. 4                 min. 3 / max. 4                         09
                                       [in. lbs.]                             min. 26.5 / max. 25
          Feeding                           optional                          optional
          Mouting on DIN top hat rail       EN 60715                          EN 60715
          Ambient air temperature        [°C] –40 … +70                       –40 … +70
          Storage temperature            [°C] –40 … +85                       –40 … +85
          Degree of protection              IP20                              IP20
          Classification acc. to NF F 16-101, NF F 16-102  I3, F2             I3, F2
          Damp Heat                         IEC 60068-2-30, 55 °C / 95 % r.h.  IEC 60068-2-30, 55 °C / 95 % r.h.
          Vibration                         IEC 60068-2-6, 5–10 Hz / 3 mm and 10–500 Hz /  IEC 60068-2-6, 5–10 Hz / 3 mm and 10–500 Hz /
                                            2 g at 0.5 x I e                  2 g at 0.5 x I e
          Random Vibration                  IEC 60068-2-64, 5–500 Hz / 2 g at 0.5 x I e  IEC 60068-2-64, 5–500 Hz / 2 g at 0.5 x I e
          Resistance to climatic conditions  IEC 60068-2-1 /-2-2 /-2-30       IEC 60068-2-1 /-2-2 /-2-30
          Standard                          IEC 60947-2                       IEC 60947-2
                                            IEC 60947-4-1                     IEC 60947-4-1
                                                                              UL 508, CSA 22.2 No. 14



          Internal resistance at 25°C ambient temperature and nominal power losses
          Rated current In                  Internal resistance Ri             Power losses Pvn
          A                                 mΩ/pole                            W/pole
          32                                2.8                                3.6
          63                                1.3                                5.7
          100                               0.7                                7.8


          Influence of ambient temperature – single mounted devices
          Rated current In   10°C  15°C  20°C  25°C  30°C   35°C  40°C   45°C  50°C   55°C   60°C  65°C   70°C
          A
          32                 38.2    37.2    35.8    35.2    34.2    33.3    32  30.7  29.8  28.8  27.8  26.5  25.1
          63                 75.3    73.2    70.6    69.3    67.4    65.5    63  60.5  58.6  56.7  54.8  52.3  49.8
          100              119.5  116.2  112  110    107    104   100    96    93     90     87    84     80
   818   819   820   821   822   823   824   825   826   827   828