Page 881 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 881

ABB  MOTOR PROTECTION AND CONTROL                                               12/28




          —
          Voltage expansion modules VI150-FBP.0, VI155-FBP.0
          Technical data



          Type                              VI150-FBP.0                       VI155-FBP.0
          Application                       only in grounded networks         in grounded and ungrounded networks


          Electrical data
          Type                              VI150-FBP.0                       VI155-FBP.0
          Supply voltaqe                    24 V DC (+ 30 %, - 20 %) (19.2 ... 31.2 V DC including ripple)
          Current consumption relay enerqized  max. 40 mA                     max. 55 mA
          Voltaqe input                     L1, L2, L3                        L1, L2, L3
          Overvoltaqe category              III in grounded networks
                                                                              II in ungrounded networks
          Nominal voltaqe input range (phase to phase)  90 - 690 V AC
                                            8 kV
          U imp
          Accuracy voltage                  +/- 2% in nominal input range
          Accuracy power factor             +/- 3.5 % in range 0.4 ... 0.95, I > 0.75 A
          Accuracy real power kW            +/- 5 % typ.
          Accuracy energy kWh               +/- 5 % typ.
          Total Harmonic Distortion THD     in %
          Rated operational voltage U e     690 V AC
          Voltage supply cables             connection cables for voltage measurement may require additional cable protection

          Digital output
          Number                            1 relay output
          Voltage switching capacity        12 … 250 V AC/DC
          Current switching                 EN 60947-5-1
          capacity             240 V AC (AC-15)  max. 1.5 A
                               120 V AC (AC-15)  max. 3 A
                               250 V DC (DC-13)  max. 0.11 A
                               125 V DC (DC-13)  max. 0.22 A
                                24 V DC (DC-13)  max. 1 A
          Minimum load for proper switching  1 W or 1 VA
          Contact wiring for inductive load  Free-wheeling diode for DC, Varistors/VDRs for AC
          Relay contact lifetime            > 500.000 switching cycles – mechanical
                                            > 100.000 switching cycles – at 250 V AC, 0.5 A
                                            > 50.000 switching cycles – at 250 V AC, 1.5 A
          Interfaces
          Interface for I/O expansion       1 for connection to UMC100.3 and/or other expansion modules
          Integrated diagnostic functions   Green LED: Device ready                                                   12
                                            Yellow LED: Diagnostics
                                            Red LED: Fault

          General data
          Type                              VI150-FBP.0                       VI155-FBP.0
          Conductor cross section           2 x 0.75 - 2.5 mm  max.
                                                        2
          Mounting                          Snap-on mounting on DIN-rail, any mounting position
                                            Min. 10 mm distance left and right to the L1 and L3 terminals required for voltages > 230 / 400 V
          Dimensions (W x H x D)            22.5 x 77 x 100 mm (excl. communication connector)
          Weight                            0.110 kg
          Degree of protection              IP20
          Temperature range                 Storage: - 25 ... + 70 °C, operation:: 0 ... + 60 °C
          Operation altitude above sea level  Max. 2000 m                     Max. 4000 m without derating
          Approvals                         ATEX, CCC, CE, cUL,EAC (other approvals on request)
                                            Shipping: ABS, DNV, GL
   876   877   878   879   880   881   882   883   884   885   886