Page 884 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 884

12/31            ABB  MOTOR PROTECTION AND CONTROL




          —
          Fieldbus communication interfaces PDP32.0, MRP31.0, DNP31.0, PDR31.0
          Technical data



          General data
          Type                           PDP32.0          MRP31.0           DNP31.0           PDR31.0
          Supply voltage                 24 V DC  -20 … +30%   24 V DC  -20% / - 20%   24 V DC    24 V DC  -20 … +30%
                                         (19.2 ... 31.2 V DC)    (19.2 … 31.2 V DC)    (11 … 24,7 V DC)   (19.2 … 31.2 V DC)
                                         incl. ripple     incl. ripple      according to DeviceNet   incl. ripple
                                                                            specification
          Current consumption            55 mA (excl. load on 5 V   Typ. 30 mA  Typ. 18.5 mA    28 mA
                                         supply for termination             (from DeviceNet)
                                         resistors)
          Communication protocol         Profibus         Modbus RTU        DeviceNet         Active Profibus DP
                                         DP-V0/DP-V1                                          termination
          Certificate                    Yes, PNO         -                 Yes, ODVA         -
          Fieldbus connection            9-pole           Removable 5-pole   Removable 5-pole   9-pole
                                         Sub-D connector or    terminal blocks  terminal blocks  Sub-D connector or
                                         terminal blocks                                      terminal blocks
          Integrated termination resistors  No            No                No                Yes
          Possible bus addresses (set via UMC100.3)  1 ... 125  1 ... 125   0 ... 63          -
          Max. baud rate                 12 MBit/s        57.6 kbaud        500 kbaud         -
          Isolated +5 V supply available for   30 mA max. -  -              -                 -
          bus termination circuitry (X3 pins 5 and 6)

          Standards / directives
          Type                           PDP32.0          MRP31.0           DNP31.0           PDR31.0
          EMC Directive                  2014/30/EC       2014/30/EC        2014/30/EC        2014/30/EC
          RoHS Directive                 2011/65/EU       2011/65/EU        2011/65/EU        2011/65/EU

          Environmental and mechanical data
          Type                           PDP32.0          MRP31.0           DNP31.0           PDR31.0
          Mounting                       On UMC100.3 or   On UMC100.3 or    On UMC100.3 or    On SMK3.0 adapter
                                         SMK3.0 adapter   SMK3.0 adapter    SMK3.0 adapter
          Mounting position              Any              Any               Any               Any
          Ambient air temperature  Operation  0 ... +60 °C  0 ... +60 °C    0 ... +60 °C      0 ... +60 °C
                                  Storage  -25 ... +70 °C  -25 ... +70 °C   -25 ... +70 °C    -25 ... +70 °C
          Vibration (sinusoidal)         0.7 g / 10 .... 150 Hz  0.7 g / 10 .... 150 Hz  0.7 g / 10 .... 150 Hz  0.7 g / 10 .... 150 Hz
          acc. to IEC/EN 60068-2-6 (Fc)
          Shock (half-sine)              15 g / 11 ms     15 g / 11 ms      15 g / 11 ms      15 g / 11 ms
          acc. to IEC/EN 60068-2-27 (Ea)
          Degree of protection           IP20             IP20              IP20              IP20
          Pollution degree               3                3                 3                 3
          Operation altitude above sea level  4000 m      4000 m            4000 m            4000 m
   12
          Duty cycle                     100 %            100 %             100 %             100 %
          Weight                         0.051 kg         0.039 kg          0.042 kg          0.047 kg
   879   880   881   882   883   884   885   886   887   888   889