Page 380 - Contactors_Catalogue
P. 380
7/10 ABB MOTOR CONTROL AND PROTECTION FOR ROLLING STOCK APPLICATIONS
—
Insulation monitoring relays
Ordering details
CM-range - Monitoring of unearthed supply systems
The high reliability of a system is guaranteed by a continuous monitoring of the resistance
between the system and the earth potential. An insulation monitoring of the CM-IWx range
recognizes these so-called insulation faults and trips as soon as the measured value of the
resistance between the system and earth potential falls below the set threshold. By using an
insulation monitoring relay already the first insulation fault will be detected and can be fixed
before a second fault occurs and forces the system to switch off.
2CDC 251 017 V0012 Choose between screw connection technology (double-chamber cage connection terminals)
and the completely tool-free Easy Connect Technology (push-in terminals) with excellent vi-
CM-IWS.2 bration resistance.
• According to IEC/EN 61557-8
• Rated control supply voltage 24 - 240 V AC/DC
CM-IWS
• For monitoring the insulation resistance of • Fault storage/latching configurable by
unearthed systems: up to U = 400 V AC control input
n
• Superimposed DC signal • 1 c/o (SPDT) contact, closed-circuit
• One measuring range 1–100 kW principle
• Precise adjustment of the threshold value
in 1 kW steps
• Interrupted wire detection
Approvals / Marks: Classifications:
A C D E K L / a, b EN 50155 (applicable parts),
IEC 60571 (applicable parts), EN 45545-2
—
Ordering details - CM-IWS
Rated Nominal System Outputs Adjustment Type Order code
control voltage leakage ca- range of the
supply U of the pacitance, specified
n
voltage = distribution max. response
measuring system to be value R
an
voltage monitored (threshold)
07
24-240 0-250 V AC / 10 μF 1-100 kW CM-IWS.1S 1SVR730660R0100
V AC/DC 0-300 V DC 1 c/o (SPDT) CM-IWS.1P 1SVR740660R0100
contact
24-240 CM-IWS.2S 1SVR730670R0200
V AC/DC 0-400 V AC 10 μF 1-100 kW CM-IWS.2P 1SVR740670R0200
* S: screw connection
P: push-in / easy connect