Page 6 - DEHN-protects-technical-building-equipment_DS197_E
P. 6

4                    1   2   3



            External lightning protection / earthing

            Lightning protection is protection against fire and, above all, personal injury.

            Lightning protection systems form a protective sheath around the building by
            intercepting direct lightning strikes and safely discharging them to the ground.                                                                                5



            Lightning and surge protection measures are essential   normative requirements and statutory provisions.
            components of the protection concept for modern buil-  IEC 62305 deals with external lightning protection and
            dings. They form the basis for preventing fire, protecting   protects buildings against the effects of a direct lightning                                       6
            people from injury and avoiding damage to vital but   strike.
            sensitive technology. Protection goals that are also based on                                                                                                                        9    8    7
                                                                                                                                                                                                              10
                                                                                                                                           10
                                                                                                                                    13  12                                                                             More information at:
            Components of a lightning protection system                                                                                          11                                                                    de.hn/earthing
            A complete lightning protection system (LPS) consists of the
            elements shown in the adjacent figure:                                                                                                                                                                     More information at:
                                                                                                                                                                                                                       de.hn/expert-pe
            External lightning protection: E.g. with HVI system
            A lightning protection system consists of an air-termination                                                             Lightning protection                                                                    Part No.
            system installed on the roof, which is connected to the            Down-conductor system  Earth-termination system
            earth-termination system via down conductors. To avoid       Air-termination    Separation distance  Lightning equipo-  1                    Supporting tube GRP / Al with air-termination tip                   105 325
            dangerous flashover and thus sparking, separation distances                            tential bonding
            must be kept to conductive metal parts. It is often not        system
            possible to maintain these separation distances consistently.
            Using a high-voltage-resistant insulated down conductor
            (HVI Conductor), however, allows you to forget about
            separation distances while still safely discharging lightning                                                           2                    Tripod, StSt                                                        105 397
            currents to the earth-termination system. An HVI system   Lightning protection system (LPS)                                                  Concrete base, 17 kg                                                102 012
            thus offers optimum safety and maximum flexibility as          according to IEC 62305
            compared to conventional lightning protection.
                                                                                                                                    3                    HVI-long Conductor, black                                           819 135

            Earthing                                          Foundation and/or ring earth electrode                                4                    Roof conductor holder for HVI Conductors                            253 015
                                                                                                                                                         Adapter for installing HVI Conductors
                                                                                                                                                                                                                             253 026
            The design and implementation of the earth-termination   Combined equipotential bonding systems are a safe and          5                    Conductor holder for HVI Conductors                                 275 250
            system are of central importance. After the concrete has set,   cost-effective earth-termination system – for as long as the
            it is no longer possible to retrofit this vital component, e.g.   building stands. Installation of a foundation earth electrode
            in the form of a foundation earth electrode. Omissions or   in new buildings is required by IEC 61364-5-54 and          6                    UNI disconnecting clamp, StSt                                       459 129
            errors during the construction phase cannot be corrected   DIN 18015-1 (German standard). The German DIN 18014
            later or, at least, not without a great deal of effort and   deals with the technical implementation. The foundation     Earthing                                                                                Part No.
            expense.                                          earth electrode is installed into the concrete foundations                                 Strip steel                                                         852 335
                                                              and covered by at least 5 cm of concrete to ensure corrosion          7                    30 x 3.5 mm, galvanised, 25 m long
                                                              protection. However, in some cases this conductive earth
                                                              connection may no longer be ensured (foundations with                 8                    Connecting clamp, St/tZn                                            308 026
                                                              increased earth contact resistance) due to various building
                                                              construction measures (e.g. when constructing a building                                   Rebar clamp DEHNclip                                                308 141
                                                              made of waterproof concrete). A corrosion-resistant ring              9                    Rd 8 mm / Fl 30 x 3-4 mm
                                                              earth electrode must then be installed in the ground outside
                                                              the building foundations and connected to the functional                                   Water-pressure-tight wall bushing for buildings made of waterproof concrete  478 540
                                                              bonding conductor in the foundations. For buildings with              10                   Connecting clamps with threaded bolt, light version                 478 129
                                                              external lightning protection systems, additional connection
                                                              lugs must be positioned at intervals corresponding to the             11                   Round steel, StSt V4A                                               860 010
                                                              relevant class of LPS in line with IEC 62305 and connected
                                                              to the ring earth electrodes. The connection lugs should                                   Cross clamp, StSt V4A                                               319 209
              Combined functional equipotential bonding system  protrude at least 1.5 m above ground level.                         12
              Foundations with increased earth contact resistance, ring earth
              electrode with functional bonding conductor according to DIN 18014                                                    13                   Anti-corrosion tape                                                 556 125
              (German standard)                                                                                                                          Tape width: 50 mm




      6                                                                                                                                                                                                                                  7
   1   2   3   4   5   6   7   8   9   10   11