 External lightning protection / earthing

 Lightning protection is protection against fire and, above all, personal injury.

 Lightning protection systems form a protective sheath around the building by
 intercepting direct lightning strikes and safely discharging them to the ground.  5



 Lightning and surge protection measures are essential   normative requirements and statutory provisions.
 components of the protection concept for modern buil-  IEC 62305 deals with external lightning protection and
 dings. They form the basis for preventing fire, protecting   protects buildings against the effects of a direct lightning   6
 people from injury and avoiding damage to vital but   strike.
 sensitive technology. Protection goals that are also based on            9    8    7
                                                                                       10
                    10
             13  12                                                                             More information at:
 Components of a lightning protection system  11                                                de.hn/earthing
 A complete lightning protection system (LPS) consists of the
 elements shown in the adjacent figure:                                                         More information at:
                                                                                                de.hn/expert-pe
 External lightning protection: E.g. with HVI system
 A lightning protection system consists of an air-termination   Lightning protection                  Part No.
 system installed on the roof, which is connected to the   Down-conductor system  Earth-termination system
 earth-termination system via down conductors. To avoid   Air-termination   Separation distance  Lightning equipo-  1  Supporting tube GRP / Al with air-termination tip  105 325
 dangerous flashover and thus sparking, separation distances   tential bonding
 must be kept to conductive metal parts. It is often not   system
 possible to maintain these separation distances consistently.
 Using a high-voltage-resistant insulated down conductor
 (HVI Conductor), however, allows you to forget about
 separation distances while still safely discharging lightning   2  Tripod, StSt                      105 397
 currents to the earth-termination system. An HVI system   Lightning protection system (LPS)   Concrete base, 17 kg  102 012
 thus offers optimum safety and maximum flexibility as   according to IEC 62305
 compared to conventional lightning protection.
             3                    HVI-long Conductor, black                                           819 135

 Earthing  Foundation and/or ring earth electrode  4  Roof conductor holder for HVI Conductors        253 015
                                  Adapter for installing HVI Conductors
                                                                                                      253 026
 The design and implementation of the earth-termination   Combined equipotential bonding systems are a safe and   5  Conductor holder for HVI Conductors  275 250
 system are of central importance. After the concrete has set,   cost-effective earth-termination system – for as long as the
 it is no longer possible to retrofit this vital component, e.g.   building stands. Installation of a foundation earth electrode
 in the form of a foundation earth electrode. Omissions or   in new buildings is required by IEC 61364-5-54 and   6  UNI disconnecting clamp, StSt  459 129
 errors during the construction phase cannot be corrected   DIN 18015-1 (German standard). The German DIN 18014
 later or, at least, not without a great deal of effort and   deals with the technical implementation. The foundation   Earthing  Part No.
 expense.  earth electrode is installed into the concrete foundations   Strip steel                   852 335
 and covered by at least 5 cm of concrete to ensure corrosion   7  30 x 3.5 mm, galvanised, 25 m long
 protection. However, in some cases this conductive earth
 connection may no longer be ensured (foundations with   8  Connecting clamp, St/tZn                  308 026
 increased earth contact resistance) due to various building
 construction measures (e.g. when constructing a building   Rebar clamp DEHNclip                      308 141
 made of waterproof concrete). A corrosion-resistant ring   9  Rd 8 mm / Fl 30 x 3-4 mm
 earth electrode must then be installed in the ground outside
 the building foundations and connected to the functional   Water-pressure-tight wall bushing for buildings made of waterproof concrete  478 540
 bonding conductor in the foundations. For buildings with   10  Connecting clamps with threaded bolt, light version  478 129
 external lightning protection systems, additional connection
 lugs must be positioned at intervals corresponding to the   11  Round steel, StSt V4A                860 010
 relevant class of LPS in line with IEC 62305 and connected
 to the ring earth electrodes. The connection lugs should   Cross clamp, StSt V4A                     319 209
 Combined functional equipotential bonding system  protrude at least 1.5 m above ground level.  12
 Foundations with increased earth contact resistance, ring earth
 electrode with functional bonding conductor according to DIN 18014   13  Anti-corrosion tape         556 125
 (German standard)                Tape width: 50 mm




 6                                                                                                                7
   2   3   4   5   6   7   8   9   10   11   12