1/120            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          MCBs
          S800S series technical features




                                                   S800S                   S803S-KM       S800S-UC
          General Data
          Tripping characteristics                 B, C, D, K,             KM             UCB, UCK
                                                   IEC/EN 60947-2,
          Standards                                EN 60898-1, UL 1077     IEC/EN 60947-2  IEC/EN 60947-2
          Poles                                    1 … 4                   3              1 … 4
          Rated current I e                 A      0.5 … 125               10 … 80        0.5 … 125
          Rated frequency f                 Hz     50/60                   50/60          50/60
          Rated insulation voltage U i  acc. to IEC/EN 60664-1  V  AC 690  AC 690         DC 1000
          Rated impulse withstand voltage U imp.  (1.2/50 µs)   kV  8      8              8
          Overvoltage category                     IV                      IV             III
          Pollution degree                         3                       3              2
          Suitability for isolation                yes                     yes            yes
          Data acc. to IEC/EN 60898-1
                                            V      AC 230/400              -              -
          Rated operational voltage U e
          Min. operating voltage            V      AC 12                   -              -
                                            kA     Char. B, C, D:          -              -
          Rated short-circuit capacity I cn
                                                   230/400 V (10 … 80A) = 25 kA
          Reference temperature for tripping characteristics  °C  30°C (Char. B, C, D)
          Electrical and Mechanical Endurance  ops  10...32 A: 10000 electrical /   -     -
                                                   10000 mechanical
                                                   40...80 A: 6000 electrical /
                                                   10000 mechanical
                                            kA     Char. B, C, D:          -              -
          Service short-circuit capacity I cs
                                                   230/400 V (10 … 80 A)
                                                   = 12.5 kA
          Data acc. to IEC/EN 60947-2
                                            V      AC 400/690
          Rated operational voltage U e
                                                   DC 125 (1-pole)                        DC 250 (1-pole)
                                                   DC 250 (2-pole)         AC 690         DC 500 (2-pole)
                                                   DC 375 (3-pole)                        DC 750 (3-pole)
                                                   DC 500 (4-pole)                        DC 750 (4-pole)
                                                                                          (63 … 125 A)
                                                                                          DC 1000 (4-pole)
                                                                                          (10 … 50 A)
          Min. operating voltage            V      AC 12                   AC 12          –
                                            kA     AC 240/415 V = 50 kA    AC 240/415 V = 50 kA  DC 250 V (1-pole) =50 kA
          Rated ultimate short-circuit capacity I cu
                                                   AC 254/440 V = 30 kA    AC 254/440 V = 30 kA  DC 500 V (2-pole) =50 kA
                                                   AC 289/500 V (up to 80 A)= 15 kA  AC 400/690 V = 6 kA  DC 750 V (3-pole) =50 kA
                                                   AC 289/500 V (100 ... 125 A)= 10 kA    DC 750 V (4-pole) (63...125A) =50 kA
                                                   AC 400/690 V (up to 80 A) = 6 kA       DC 1000V (4-pole)(10...50A) = 50 kA
                                                   AC 400/690 V (100 … 125 A) = 4.5 kA  DC 375 V = 30 kA
                                                   DC 125 V (1-pole) = 30 kA
                                                   DC 250 V (2-pole) = 30 kA
                                                   DC 375 V (3-pole) = 30 kA
                                                   DC 500 V (4-pole) = 30 kA
                                            kA     AC 240/415 V = 40 kA                   DC 250 V (1-pole) =50 kA
          Rated service short-circuit capacity I cs
                                                   AC 254/440 V (up to 80 A) = 22.5 kA    DC 500 V (2-pole) =50 kA
                                                   AC 254/440 V (100 … 125 A) = 15 kA     DC 750 V (3-pole) =50 kA
                                                   AC 289/500 V (up to 80 A) = 11 kA      DC 750 V (4-pole) (63...125A) =50 kA
                                                   AC 289/500 V (100 … 125 A) = 5 kA      DC 1000V (4-pole)(10...50A) = 50 kA
                                                   AC 400/690 V (up to 80 A) = 4 kA
                                                   AC 400/690 V (100 … 125 A) = 3 kA  DC 375 V = 30 kA
                                                   DC 125 V (1-pole) = 30 kA
                                                   DC 250 V (2-pole) = 30 kA
                                                   DC 375 V (3-pole) = 30 kA
                                                   DC 500 V (4-pole) = 30 kA
          Reference temperature for tripping characteristics  °C  B, C, D: 30 °C          UCB: 30 °C
                                                   K: 40 °C                only magnetic release  UCK: 40 °C
         Electrical and Mechanical Endurance  ops.  0.5...32 A: 10000 electrical / 10000   10 … 32 A: 10 000   0.5...100 A: 1500 electrical /
                                                   mechanical              electrical/ 10000   10000 mechanical
                                                   40...100 A: 6000 electrical / 10000   mechanical  125 A: 1000 electrical /
                                                   mechanical              40 ... 80 A:    8000 mechanical
                                                   125 A: 4000 electrical / 8000   6000 electrical/
                                                   mechanical              4000 mechanical
          Data acc. to UL 1077/ C22.2 No 235, Supplementary Protector
          Alternating current:                     1
          int. cap.                                240: 30 (0.5…63A)
                                                   277: 14 (0.5…63A)
                                                   347: 6 (0.5…63A)
                                                   2,3,4
                                                   240: 30 (0.5...63A)
                                                   480 Y/277: 14 (0.5…63A)
                                                   600 Y/347: 6 (0.5…63A)