1/124            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          MCBs
          S800C series technical features




                                                              S800C
          General Data
          Tripping characteristics                            B, C, D, K
          Standards                                           IEC/EN 60947-2,EN 60898-1, UL 1077
          Poles                                               1 … 4
          Rated current I e                     A             10 … 125
          Rated frequency f                     Hz            50/60
          Rated insulation voltage U i  acc. to IEC/EN 60664-1  V  AC 500
          Rated impulse withstand voltage U imp.  (1.2/50 µs)   kV  8
          Overvoltage category                                IV
          Pollution degree                                    3
          Suitability for isolation                           yes
          Data acc. to IEC/EN 60898-1
                                                V             AC 230/400
          Rated operational voltage U e
          Min. operating voltage                V             AC 12
                                                kA            15 kA
          Rated short-circuit capacity I cn
          Reference temperature for tripping characteristics  °C  30°C (Char. B, C, D)
          Electrical and Mechanical Endurance   ops           10 … 32 A: 10 000 electrical/10 000 mechanical
                                                              40 … 100 A: 6000 electrical/10 000 mechanical
                                                              125 A: 4000 electrical/8 000 mechanical
                                                kA            Char. B, C, D: 230/400 V = 7.5 kA
          Service short-circuit capacity I cs
          Data acc. to IEC/EN 60947-2
                                                V             AC 254/440
          Rated operational voltage U e
                                                              DC 125 (1-pole)
                                                              DC 250 (2-pole)
                                                              DC 375 (3-pole)
                                                              DC 500 (4-pole)
          Min. operating voltage                V             AC 12
                                                kA            AC 240/415 V = 25 kA
          Rated ultimate short-circuit capacity I cu
                                                              AC 254/440 V = 15 kA
                                                              DC 125 V (1-pole) = 10 kA
                                                              DC 250 V (2-pole) = 10 kA
                                                              DC 375 V (3-pole) = 10 kA
                                                              DC 500 V (4-pole) = 10 kA
                                                kA            AC 240/415 V = 18 kA
          Rated service short-circuit capacity I cs
                                                              AC 254/440 V = 10 kA
                                                              DC 125 V (1-pole) = 10 kA
                                                              DC 250 V (2-pole) = 10 kA
                                                              DC 375 V (3-pole) = 10 kA
                                                              DC 500 V (4-pole) = 10 kA
          Reference temperature for tripping characteristics  °C   B, C, D: 30 °C
                                                              K: 40 °C
          Electrical and Mechanical Endurance   ops.          6 … 32 A: 10 000 electrical/10 000 mechanical
                                                              40 … 100 A: 6000 electrical/10 000 mechanical
                                                              125  A: 4000 electrical/8 000 mechanical
          Mechanical Data
          Housing                                             Material group I, RAL 7035
          Toggle                                              black, lockable
          Classification acc. To NF F 126-101, NF F 16-102    I3, F2
          Protection degree acc. to EN 60529                  IP20; IP40 (actuating end only)
          Shock resistance acc. to IEC/EN 60068-2-30          IEC 61373 Cat. 1 Class B, 5g / 30ms acc. To IEC 60068-27 Test Ea
          Vibration resistance acc. to IEC/EN 60068-2-6       IEC 60068-2-6 Test Fc;
                                                              2–13.2 Hz/1 mm
                                                              13.2–100 Hz/0.7 g
                                                              with load 100 % x I e
          Environmental conditions (damp heat)   °C/RH        12 + 12 cycle with 55 °C/90–96 %
          acc. to IEC/EN 60068-2-30                           and 25 °C/95–100 %
          Environmental conditions (dry heat)   °C/RH         16 hours 55 °C/2 hours 70 °C with
          acc. to IEC/EN 60068-2-2 Test B                     damp heat 55 %
          Ambient temperature                   °C            –25 … +60
          Storage temperature                   °C            –40 … +70
          Data acc. to UL 1077/ C22.2 No 235, Supplementary Protector
          Alternating current:                                1
          int. cap.                                           240: 20(≤ 100A)
                                                              277: 10 (≤ 100A)
                                                              2,3,4
                                                              240: 20 (≤ 100A)
                                                              480 Y/277: 10 (≤ 100A)
          Direct current:                                     1
          int. cap.                                           125: 10 (≤ 100A)
                                                              2, 3, 4
                                                              250: 10 (2P, ≤ 100A)
                                                              375: 10 (3P, ≤ 100A)
                                                              500: 10 (4P, ≤ 100A)