1/122            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          MCBs
          S800N series technical features




                                                              S800N
          General Data
          Tripping characteristics                            B, C, D
          Standards                                           IEC/EN 60947-2, EN 60898-1
          Poles                                               1 … 4
          Rated current I                            A        6 … 125
                   e
          Rated frequency f                          Hz       50/60
          Rated insulation voltage U  acc. to IEC/EN 60664-1  V  AC 690
                          i
          Rated impulse withstand voltage U   (1.2/50 µs)   kV  8
                                imp.
          Overvoltage category                                IV
          Pollution degree                                    3
          Suitability for isolation                           yes
          Data acc. to IEC/EN 60898-1
          Rated operational voltage U e              V        AC 230/400
          Min. operating voltage                     V        AC 12
          Rated short-circuit capacity I cn          kA       AC 230/400 V (10 … 80 A) = 20 kA
          Reference temperature for tripping characteristics  °C  30°C (Char. B, C, D)
          Electrical and Mechanical Endurance        ops      10...32 A: 10000 electrical / 10000 mechanical
                                                              40...80 A: 6000 electrical / 10000 mechanical
          Service short-circuit capacity I  cs       kA       230/400 V (10 … 80 A) = 10 kA
          Data acc. to IEC/EN 60947-2
          Rated operational voltage U e                       AC 400/690
                                                     V        DC 125 (1-pole)
                                                              DC 250 (2-pole)
                                                              DC 375 (3-pole)
                                                              DC 500 (4-pole)
          Min. operating voltage                     V        AC 12
          Rated ultimate short-circuit capacity I    kA       AC 240/415 V = 36 kA
                                  cu
                                                              AC 254/440 V = 20 kA
                                                              AC 289/500 V = 10 kA
                                                              AC 400/690 V = 4.5 kA
                                                              DC 125 V (1-pole) = 20 kA
                                                              DC 250 V (2-pole) = 20 kA
                                                              DC 375 V (3-pole) = 20 kA
                                                              DC 500 V (4-pole) = 20 kA
          Rated service short-circuit capacity I     kA       AC 240/415 V = 30 kA
                                 cs
                                                              AC 254/440 V (up to 63 A) = 15 kA
                                                              AC 254/440 V (80 … 125 A) = 10 kA
                                                              AC 289/500 V (up to 80 A) = 8 kA
                                                              AC 289/500 V (100 ... 125) = 5 kA
                                                              AC 400/690 V = 3 kA
                                                              DC 125 V (1-pole) = 20 kA
                                                              DC 250 V (2-pole) = 20 kA
                                                              DC 375 V (3-pole) = 20 kA
                                                              DC 500 V (4-pole) = 20 kA
          Reference temperature for tripping characteristics  °C   30 °C

          Electrical and Mechanical Endurance        ops.     6 … 32 A: 10 000 electrical/10000 mechanical
                                                              40 … 100 A: 6000 electrical/10000 mechanical
                                                              125  A: 4000 electrical/8000 mechanical
          Mechanical Data
          Housing                                             Material group I, RAL 7035
          Toggle                                              black, lockable
          Classification acc. To NF F 126-101, NF F 16-102    I3, F2
          Protection degree acc. to EN 60529                  IP20; IP40 (actuating end only)
          Shock resistance acc. to IEC/EN 60068-2-30          IEC 61373 Cat. 1 Class B, 5g / 30ms acc. To IEC 60068-27 Test Ea
          Vibration resistance acc. to IEC/EN 60068-2-6       IEC 60068-2-6 Test Fc;
                                                              2–13.2 Hz/1 mm
                                                              13.2–100 Hz/0.7 g
                                                              with load 100% x I e
          Environmental conditions (damp heat)       °C/RH    12 + 12 cycle with 55 °C/90–96 %
          acc. to IEC/EN 60068-2-30                           and 25 °C/95–100 %
          Environmental conditions (dry heat)        °C/RH    16 hours 55 °C/2 hours 70 °C with
          acc. to IEC/EN 60068-2-2 Test B                     damp heat 55 %
          Ambient temperature                        °C       – 25 … +60
          Storage temperature                        °C       – 40 … +70