Page 136 - Din prodcuts 2020
P. 136

1/126            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201
  1



          —
          MCBs
          S800B series technical features




                                                              S800B
          General Data
          Tripping characteristics                            B, C, D, K
          Standards                                           IEC/EN 60947-2,EN 60898-1
          Poles                                               1 … 4
          Rated current I e                          A        32 … 125
          Rated frequency f                          Hz       50/60
          Rated insulation voltage U i  acc. to IEC/EN 60664-1  V  AC 500
          Rated impulse withstand voltage U imp.  (1.2/50 µs)   kV  6
          Overvoltage category                                III
          Pollution degree                                    3
          Suitability for isolation                           yes
          Data acc. to IEC/EN 60898-1
                                                     V        AC 230/400
          Rated operational voltage U e
          Min. operating voltage                     V        AC 12
                                                     kA       AC 230/400 = 10 kA
          Rated short-circuit capacity I cn
          Reference temperature for tripping characteristics  °C  B, C, D: 30°C
          Electrical and Mechanical Endurance        ops.     4000
                                                     kA       AC 230/400 V = 7.5 kA
          Service short-circuit capacity I cs
          Data acc. to IEC/EN 60947-2
                                                     V        AC 230/400
          Rated operational voltage U e
          Min. operating voltage                     V        AC 12
                                                     kA       AC 230/400 V = 16 kA
          Rated ultimate short-circuit capacity I cu
                                                              DC 75 V (1-pole) = 10 kA
                                                              DC 150 V (2-pole) = 10 kA
                                                              DC 225 V (3-pole = 10 kA
                                                              DC 300 V (4-pole) = 10 kA
                                                     kA       10 kA
          Rated service short-circuit capacity I cs
          Reference temperature for tripping characteristics  °C   B, C, D: 30 °C        K: 40 °C
          Electrical and Mechanical Endurance        ops.     32...100 A: 1500 electrical / 10000 mechanical
                                                              125 A: 1000 electrical / 8000 mechanical
          Mechanical Data
          Housing                                             Material group I, RAL 7035
          Toggle                                              black, lockable
          Classification acc. To NF F 126-101, NF F 16-102    I3, F2
          Protection degree acc. to EN 60529                  IP20; IP40 (actuating end only)
          Shock resistance acc. to IEC/EN 60068-2-30          -
          Vibration resistance acc. to IEC/EN 60068-2-6       -
          Environmental conditions (damp heat)       °C/RH    -
          acc. to IEC/EN 60068-2-30
          Environmental conditions (dry heat)        °C/RH    -
          acc. to IEC/EN 60068-2-2 Test B
          Ambient temperature                        °C       –25 … +60
          Storage temperature                        °C       –40 … +70
          Installation
          Terminal                                            Failsafe cage or ringlug terminal
          Connections (top/bottom) – C u  only       mm 2     1 … 50 stranded
                                                               1 … 70 flexible
          Tightening torque                          Nm       3.5
                                                     in-Ibs.  31
          Screwdriver                                         POZI 2
          Mounting                                            EN 60715
          Mounting position                                   any
          Supply                                              any
          Dimensions and weight
          Pole dimensions (H x L x W)                mm       82.5 x 95 x 26.5
          Pole weight                                g        ca. 240
   131   132   133   134   135   136   137   138   139   140   141