Page 137 - Din prodcuts 2020
P. 137
1/127 1
—
MCBs
S800HV series technical features
S800HV
General Data
Tripping characteristics C, K
Standards IEC/EN 60947-2, UL 1077
Poles 1 … 3
Rated frequency f Hz 50/60
Overvoltage category III
Pollution degree 2
Suitability for isolation yes
Data acc. to IEC/EN 60947-2
Rated operational voltage U V AC 580/1000
e
Min. operating voltage V AC 12
A 0.5 ... 125
Rated operational current I n
kA 1.5 (0.5...5 A)
Rated ultimate short-circuit capacity I cu
4 (6 … 63 A)
3 (80 … 125 A)
kA 1.5 (0.5 ... 5 A)
Rated service short-circuit capacity I cs
2.5 (6 … 63 A)
2 (80 … 125 A)
Reference temperature for tripping characteristics °C 40 °C
Electrical and Mechanical Endurance ops. 0.5 ... 100 A: 1500 electrical/10000 mechanical
125 A: 1000 electrical/8000 mechanical
Data according to UL 1077/ C22.2 No 235, Supplementary Protector
Alternating current 600 Y/347: 15
(3P, 10…32A)*
Mechanical Data
Housing Material group I, RAL 7035
Toggle black, lockable
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Classification acc. To NF F 126-101, NF F 16-102 I3, F2
Classification acc. to IEC 61373 Cat. 1, Class B
(shock and vibration)
Shock resistance acc. to IEC/EN 60068-2-27 Test Ea: 5 g / 30 ms
Vibration resistance acc. to IEC/EN 60068-2-6 Test Fc:
2–13.2 Hz/1 mm
13.2–100 Hz/0.7 g
with load 100 % x I
e
Environmental conditions (damp heat) °C/RH 12 + 12 cycle with 55 °C/90–96 %
acc. to IEC/EN 60068-2-30 and 25 °C/95–100 %
Environmental conditions (dry heat) °C/RH 16 hours 55°C / 2 hours 70°C / 55% RH
acc. to IEC/EN 60068-2-2 Test B
Ambient temperature °C –25 … +60
Storage temperature °C –40 … +70
Installation
Terminal Failsafe cage terminal
Connections (top/bottom) – C u only mm 2 1 … 50 stranded
1 … 70 flexible
Tightening torque Nm 3.5
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply any
Dimensions and weight
Pole dimensions (H x L x W) mm 142 x 82.5 x 26.5
Pole weight kg 0.27
* 3P, 10 ... 32 A - only valid with XT2L 125 TMF 35-400