Page 27 - Din prodcuts 2020
P. 27

1/17      1




          —
          High performance circuit-breakers
          Selection table











 S 750 DR  S800S  S800N  S800C  S800B  S800HV        S800U           S804U-           S804U-           S800PV-

 Series  S 700                                                        UCZ              PVS              SP
 Characteristics  E selective, E selective,
 K selective K selective *9  B, C, D  K  KM  UCB  UCK  B, C, D  B, C, D, K  B, C, D, K  C, K  Z, K  UCZ  PVS  PV-SP
 Rated current [A]  16 ≤   10 ≤   0.5 ≤   0.5 ≤   20 ≤   0.5 ≤   0.5 ≤   6 ≤   10 ≤   10 ≤     5 ≤
 In   In   In   In   In   In   In   In   In   32 ≤  C: 10 ≤ In ≤ 32  In   10-80  5             In
 ≤ 63  ≤ 100  ≤ 125  ≤ 125  ≤ 80  ≤ 125  ≤ 125  ≤ 125  ≤ 125  In ≤ 125  K: 6 ≤ In ≤ 125  ≤ 100  ≤ 125
 IEC/EN   Ics  1,   24
 60947-2  1P+N 60
 Direct current  125  30  30  20  10
 T=I/R≤5ms   220
 for   250  50  50
 all series,   2  48
 except S280   125
 UC and   250  30  30  20  10
 S800S-UC,
 where   440
 T=I/R<15ms   500  50  50
 800                                                                                           5
 3,4  375  30  *6  30  *6  30  *6  20  *6  10  *6
 500  30  *7  30  *7  20  *7  10  *7
 750  50  *6  50  *6
 50 (63 ... 125 A)  *7  50 (63 ... 125 A)  *7
 1000  50 (10 ... 50 A)  *7  50 (10 ... 50 A)  *7
 1200                                                                                          5  *5
 UL 1077/   Int.  1,   120
 C22.2   cap. 1P+N 240  30    30
 No 235  (0.5...63 A) (0.5...63 A)  20 (≤ 100 A)
 Alternating   277  14    14
 current  (0.5...63 A) (0.5...63 A)
 347  6 (0.5...63 A) 6 (0.5...63 A)  10 (≤ 100 A)
 2, 3, 4 240
 480   14 (0.5...   14 (0.5...
 Y/277  63 A)  *27  63 A)  *27  10 (≤100 A)
 600Y/347  6    6          15 (3P, 10 ... 32 A)  *28
 (0.5...63 A) (0.5...63 A)
 UL 1077/   Int.  1,   60
 C22.2   cap. 1P+N 125  10 (≤ 100 A)
 No 235    250
 Direct current  2, 3, 4 125
 250     10 (2P,
 ≤ 100 A)
 375  10 (3P,
 ≤ 100 A)
 500  10 (4P,
 ≤ 100 A)
 UL 489/ C22.2  Int.  1   240               30
 No 5  cap.  277
 Alternating   2, 3, 4 240                  50
 current  480
 Y/277
 UL 489/ C22.2  Int. 1  60
 No 5  cap. 2  125
 Direct current
 4  600                                                      10
 UL489B    4  1000                                                            3
   Direct current


          *13   > 25 A              *18   > 40 A              *24  by 150V DC 2-pole    *28   3P, 10 ... 32 A - only valid with
          *15   only 2 poles (connection in series)  *19   ≤ 35 A  *25  by 225V DC 3-pole  XT2L 125 TMF 35-400
          *16   UL 1077 only        *20  10-80 A              *26  by 300V DC 4-pole
          *17   ≤ 40 A              *23  by 75V DC 1-pole     *27   certification 50A ongoing
   22   23   24   25   26   27   28   29   30   31   32