Page 30 - Din prodcuts 2020
P. 30
1/20 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
1
—
MCBs
S 200 technical features
S 200 S 200 M S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
General Standards IEC/EN 60898-1, IEC/EN 60898-1, IEC/EN 60898-2, IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1 IEC/EN 60947-2 IEC/EN 60947-
Data IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 2
UL 1077 UL 1077, CSA 22.2 UL 1077, CSA 22.2 UL 1077, CSA 22.2 UL 1077, UL 489, UL 489, UL 489
No. 235 No. 235 No. 235 CSA 22.2 No. 235 CSA22.2 No.5 CSA22.2 No.5
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P, 1P+N, 1P, 2P, 3P, 4P 1P, 3P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P
3P+N
S 200 Tripping characteristics B, C, D, K, Z B, C, K, Z B, C, D, K, Z K B, C C, K, Z K
Rated current I n A 0.5…63 A 0.2…63 A 6…20 A 0.2…63 A 0.2…25 A 0.2…63 A 1…63 A
Rated frequency f Hz 50 / 60 Hz 0 / 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz DC
Rated insulation voltage U acc. to IEC/EN 60664-1 V 440 V AC (phase to phase) 440 V AC (phase to phase)
i
Overvoltage category III --
Pollution degree 3 2 --
Data acc. to Rated operational voltage U n V 1P: 230/400 V AC; 1P+N: 230 V AC ; 1P: 230 V AC, 220 V DC 1P: 230 V AC, --
IEC/EN 2...4P: 400 V AC; 3P+N: 400 V AC 2P: 400 V AC, 440 V DC 3P: 440 V AC
60898-1 3...4P: 400 V AC*
(except Max. power frequency recovery voltage (U ) V 1P: 253 V AC; 1P+N: 253 V AC; 1P: 253 V AC, 250 V DC 1P: 253 V AC, --
S 200 M UC max 2P: 440 V AC; 3...4P: 440 V AC; 3P+N: 440 V AC; 2P: 440 V AC, 500 V DC 3P: 440 V AC
data acc. to 1P: 72 V DC; 2P: 125 V DC 3...4P:440 V AC*
IEC/EN
60898-2) Min. operating voltage V 12 V AC - 12 V DC 12 V AC --
Rated short-circuit capacity I cn kA 6 kA 10 kA 10 kA ≤ 25 A: 25 kA 6 kA --
> 25 A: 15 kA
Energy limiting class (B, C up to 40 A) 3 --
Rated impulse withstand voltage Uimp. (1.2/50µs) kV 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) --
Dielectric test voltage kV 2 kV (50 / 60Hz, 1 min.) --
Reference temperature for tripping characteristics °C B, C, D: 30°C 30 °C B, C: 30 °C --
Electrical endurance ops. In < 32A: 20,000 ops (AC), 20,000 ops. --
In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC);
(1 cycle 2s - ON, 13s - OFF, In ≤ 32A),
(1 cycle 2s - ON, 28s - OFF, In > 32A)
Data acc. to Rated operational voltage U V 1P: 230 V AC; 1P+N: 230 V AC; 2...4P: 440 V AC; 1P: 253 V AC, 220 V DC 1P: 230 V AC; 1P: 230 V AC 1P: 230 V AC 1P: 230 V AC --
e
IEC/EN 3P+N: 440 V AC 2...4P: 440 V AC, 440 1P+N: 230 V AC; 2...4P: 400 V AC 2...4P: 400 V AC 2...4P: 400
60947-2 V DC 2...4P: 400 V AC; V AC
3P+N: 400 V AC
Max. power frequency recovery voltage (U max ) V 1P: 253 V AC; 1P+N: 253 V AC; 2P...4P: 462 V AC; 1P: 266 V AC, 250 V DC 1P: 253 V AC; 1P: 253 V AC 1P: 253/440 V AC; 1P: 253 V AC --
3P+N: 462 V AC; 1P: 72 V DC; 2P: 125 V DC 2...4P: 462 V AC, 500 1P+N: 253 V AC; 2...4P: 440 V AC 2...4P: 440 V AC 2...4P: 440
V DC 2P...4P: 440 V AC; V AC
3P+N: 440 V AC;
1P: 72 V DC; 2P: 125
V DC
Min. operating voltage V 12 V AC - 12 V DC 12 V AC 12 V AC --
Rated ultimate short-circuit breaking capacity I kA 10 kA 15 kA ≤ 40 A: 10 kA AC; 10 ≤ 25 A: 25 kA 15 kA 10 kA 15 kA --
cu
kA DC ≥ 32 A: 15 kA
> 40 A: 6 kA AC; 10 kA
DC
Rated service short-circuit breaking capacity I cs kA 7.5 kA ≤ 40 A: 11.2 kA ≤ 40 A: 7,5 kA AC; 10 ≤ 25 A: 12.5 kA ≤ 40 A: 11.2 kA; 7.5 kA ≤ 40 A: 11.2 kA; --
50, 63 A: 7.5 kA kA DC ≤ 32…40 A: 11.2 kA > 40 A: 7.5 kA > 40 A: 7.5 kA
> 40 A: 6 kA(AC; 10 50, 63 A: 7.5 kA AC; (AC);
kA DC
Rated impulse withstand voltage Uimp. (1.2/50µs) kV 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) --
Dielectric test voltage kV 2 kV (50 / 60Hz, 1 min.) --
Reference temperature for tripping characteristics °C B, C, D: 55°C; K, Z: 20°C B, C: 55 °C; K, Z: 20 °C 20 °C C, K, Z: 20°C 20 °C --
Electrical endurance ops. In < 32A: 20,000 ops (AC), In < 32A: 20,000 ops In < 32A: 20,000 ops In < 25A: 20,000 In < 25A: --
In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC); (AC), (AC), In ≥ 32A: 10,000 ops (AC), 20,000 ops
(1 cycle 2s - ON, 13s - OFF, In ≤ 32A), In ≥ 32A: 10,000 ops. ops. (AC); In ≥ 25A: 10,000 (AC),
(1 cyle 2s - ON, 28s - OFF, In > 32A) (AC); 1,000 ops. (DC); ops. (AC); In ≥ 25A:
1,500 ops. (DC); (1 cycle 2s - ON, 13s - 10,000 ops.
OFF, (AC);
In ≤ 32A), (1 cyle 2s -
ON, 28s - OFF, In ≥ 32A)
Note:
* Only acc. to IEC/EN 60898-1