Page 31 - Din prodcuts 2020
P. 31

1/21       1




          —
          MCBs
          S 200 technical features




    S 200  S 200 M  S 200 M UC  S 200 P     S 200 MR     S 200 S      SU 200 M            SU 200 MR  S 200 UDC
 General   Standards     IEC/EN 60898-1,   IEC/EN 60898-1,   IEC/EN 60898-2,   IEC/EN 60898-1,  IEC/EN 60947-2  IEC/EN 60898-1  IEC/EN 60947-2  IEC/EN 60947-
 Data  IEC/EN 60947-2  IEC/EN 60947-2  IEC/EN 60947-2  IEC/EN 60947-2                     2
    UL 1077  UL 1077, CSA 22.2   UL 1077, CSA 22.2   UL 1077, CSA 22.2    UL 1077,   UL 489,   UL 489,   UL 489
    No. 235   No. 235      No. 235          CSA 22.2 No. 235          CSA22.2 No.5        CSA22.2 No.5

    Poles     1P, 2P, 3P, 4P, 1P+N, 3P+N  1P, 2P, 3P, 4P  1P, 2P, 3P, 4P, 1P+N,   1P, 2P, 3P, 4P  1P, 3P  1P, 2P, 3P, 4P  1P, 2P, 3P, 4P  1P, 2P
                           3P+N
    Tripping characteristics     B, C, D, K, Z  B, C, K, Z  B, C, D, K, Z  K  B, C  C, K, Z  K

 Rated current I n  A  0.5…63 A  0.2…63 A                6…20 A       0.2…63 A   0.2…25 A  0.2…63 A  1…63 A
 Rated frequency f  Hz  50 / 60 Hz  0 / 50 / 60 Hz  50 / 60 Hz  50 / 60 Hz                           DC
 Rated insulation voltage U  acc. to IEC/EN 60664-1  V  440 V AC (phase to phase)  440 V AC (phase to phase)
 i
 Overvoltage category     III                                                                        --
 Pollution degree     3  2                                                                           --
 Data acc. to  Rated operational voltage U n  V  1P: 230/400 V AC; 1P+N: 230 V AC ;   1P: 230 V AC, 220 V DC  1P: 230 V AC,  --
 IEC/EN   2...4P: 400 V AC; 3P+N: 400 V AC  2P: 400 V AC, 440 V DC  3P: 440 V AC
 60898-1  3...4P: 400 V AC*
 (except   Max. power frequency recovery voltage  (U  )  V  1P: 253 V AC; 1P+N: 253 V AC;   1P: 253 V AC, 250 V DC  1P: 253 V AC,  --
 S 200 M UC   max  2P: 440 V AC; 3...4P: 440 V AC; 3P+N: 440 V AC;   2P: 440 V AC, 500 V DC  3P: 440 V AC
 data acc. to   1P: 72 V DC; 2P: 125 V DC  3...4P:440 V AC*
 IEC/EN
 60898-2)  Min. operating voltage  V  12 V AC - 12 V DC  12 V AC      --
 Rated short-circuit capacity I cn  kA  6 kA  10 kA  10 kA    ≤ 25 A:   25 kA  6 kA  --
                             > 25 A:   15 kA
 Energy limiting class (B, C up to 40 A)     3                        --
 Rated impulse withstand voltage Uimp. (1.2/50µs)   kV  4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)  --
 Dielectric test voltage  kV  2 kV (50 / 60Hz, 1 min.)                --
 Reference temperature for tripping characteristics  °C  B, C, D: 30°C  30 °C  B, C: 30 °C  --
 Electrical endurance  ops.  In < 32A: 20,000 ops (AC),   20,000 ops.  --
 In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC);
 (1 cycle 2s - ON, 13s - OFF, In ≤ 32A),
 (1 cycle 2s - ON, 28s - OFF, In > 32A)
 Data acc. to  Rated operational voltage U    V  1P: 230 V AC; 1P+N: 230 V AC; 2...4P: 440 V AC;   1P: 253 V AC, 220 V DC  1P: 230 V AC;   1P: 230 V AC  1P: 230 V AC  1P: 230 V AC  --
 e
 IEC/EN   3P+N: 440 V AC   2...4P: 440 V AC, 440   1P+N: 230 V AC;   2...4P: 400 V AC  2...4P: 400 V AC  2...4P: 400
 60947-2  V DC             2...4P: 400 V AC;                                              V AC
                           3P+N: 400 V AC
 Max. power frequency recovery voltage (U max )  V  1P: 253 V AC; 1P+N: 253 V AC; 2P...4P: 462 V AC;   1P: 266 V AC, 250 V DC  1P: 253 V AC;   1P: 253 V AC  1P:  253/440 V AC;   1P: 253 V AC  --
 3P+N: 462 V AC; 1P: 72 V DC; 2P: 125 V DC  2...4P: 462 V AC, 500   1P+N: 253 V AC;   2...4P: 440 V AC  2...4P: 440 V AC  2...4P: 440
          V DC             2P...4P: 440 V AC;                                             V AC
                           3P+N: 440 V AC;
                           1P: 72 V DC; 2P: 125
                           V DC
 Min. operating voltage  V  12 V AC - 12 V DC  12 V AC                12 V AC                        --
 Rated ultimate short-circuit breaking capacity I  kA  10 kA  15 kA  ≤ 40 A: 10 kA AC; 10   ≤ 25 A:   25 kA  15 kA  10 kA  15 kA  --
 cu
          kA DC            ≥ 32 A:   15 kA
          > 40 A: 6 kA AC; 10 kA
          DC
 Rated service short-circuit breaking capacity I cs  kA  7.5 kA  ≤ 40 A:   11.2 kA  ≤ 40 A: 7,5 kA AC; 10   ≤ 25 A:   12.5 kA  ≤ 40 A: 11.2 kA;  7.5 kA  ≤ 40 A: 11.2 kA;  --
 50, 63 A:    7.5 kA  kA DC  ≤ 32…40 A:   11.2 kA  > 40 A: 7.5 kA                         > 40 A: 7.5 kA
          > 40 A: 6 kA(AC; 10   50, 63 A:    7.5 kA  AC;                                  (AC);
          kA DC
 Rated impulse withstand voltage Uimp. (1.2/50µs)   kV  4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)  --
 Dielectric test voltage  kV  2 kV (50 / 60Hz, 1 min.)                                               --
 Reference temperature for tripping characteristics  °C  B, C, D: 55°C; K, Z:   20°C  B, C: 55 °C; K, Z: 20 °C  20 °C   C, K, Z:   20°C  20 °C  --
 Electrical endurance  ops.  In < 32A: 20,000 ops (AC),   In < 32A: 20,000 ops   In < 32A: 20,000 ops   In < 25A: 20,000   In < 25A:   --
 In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC);   (AC),   (AC), In ≥ 32A: 10,000   ops (AC),   20,000 ops
 (1 cycle 2s - ON, 13s - OFF, In  ≤ 32A),   In ≥ 32A: 10,000 ops.   ops. (AC);   In ≥ 25A: 10,000   (AC),
 (1 cyle 2s - ON, 28s - OFF, In > 32A)  (AC);   1,000 ops. (DC);   ops. (AC);             In ≥ 25A:
          1,500 ops. (DC);  (1 cycle 2s - ON, 13s -                                       10,000 ops.
                           OFF,                                                           (AC);
                           In  ≤ 32A), (1 cyle 2s -
                           ON, 28s - OFF, In ≥ 32A)
   26   27   28   29   30   31   32   33   34   35   36