Page 422 - Din prodcuts 2020
P. 422
4/68 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Auxiliary elements for S800
S800-AUX/ALT
4
Technical data
Combined auxiliary and signal contact S800-AUX/ALT
Utilisation categories AC15 400/2 A,
compliant to IEC 60947-5-1 AC15 240/6 A
DC13 250/0.55 A
DC13 125 V/1.1 A
DC13 60 V/2 A
DC13 24 V/4 A
Rated values compliant to UL 489 125 VAC/6 A
250 VAC/5 A
24 V DC/4 A
125 V DC/0.3 A
250 V DC/0.15 A
Conventional free air thermal current I A 6
th
Minimum operational I min mA 3
Minimum operational voltage U min V 24
Rated insulation voltage U A 690
i
Number of contacts 2 (1x AUX, 1x AUX/ALT)
Rated impulse withstand voltage U imp kV 6
Pollution degree 3
Standard IEC 60947-5-1 / UL 489
Contact function Changeover contact
Connection C u mm 2 1 x 2.5
2 x 1.5
14 AWG
Tightening torque Nm 1
AC/DC feed. any
Mounting on DIN top hat rail EN 60715
Protection category IP20
Permissible operating ambient temperature °C -25 ... +60
Storage temperature °C -40 ... +70
Mech. lifetime of device 6000 switching cycles
I with S450E A 1000
cu
Vibration resistance IEC 60068-2-6;
EN 61373 Cat.1/Class B
5 g, 20 frequency cycle 5 ... 150 ... 5 Hz
at 24 V AC/DC, 5 mA short-term interruption <10 ms
GTIN Order details Price Weight Pack
761227 1 1 piece unit
Article EAN Type code Order code piece kg pc.
Auxiliary/signal contact 1206819 S800-AUX/ALT 2CCS800900R0021 0.05 1