Page 424 - Din prodcuts 2020
P. 424

4/70             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Auxiliary elements for S800
          S800-RSU system




  4
                                    S800-RSU-H IEC version
                                    S800W-RSU World version
                                    Remote Switching Units for High Performance MCB
                                    The S800-RSU makes the use of S800 even more convenient. Driven by a brushless high
                                    precision DC motor, S800-RSU ensures fast remote-controlled operation.

                                    Mounting ability
                                    The S800-RSU is mountable on any multipole S800 High Performance MCB. Wiring and
                                    operation is feasible on field. The connection has to be done by a 10-pole Micro Fit 3.0
                                    (not included in delivery). S800-RSU operated with standard MDRC pushbuttons and indica-
                                    tor lights or can be done via programmable logic controllers (PLCs).
                                    Switching times
                                    OFF –> ON                    <<500 ms
                                    from signal to contact closing

                                    ON –> OFF                    <<250 ms
                                    from signal to contact opening

                                    TRIP –> OFF –> ON            <<1500 ms
                                    from signal to contact closing
                                    For differing requirements, please contact your local ABB partner

                                    Safety Intelligence
                                    •  When detecting manual use, inputs are deactivated for 10 seconds
                                    •  If the spindle is rotated more than 360°, all outputs become active
                                    •  Manual switch off via lever is possible (S803, S804)
                                    •  Manual switch on via lever is not possible (S802)
                                    •  RSU is locked for five minutes after three switching attempts leading to a trip
                                    •  Mechanical fixation via lock slider blocking the spindle


                                    S800-RSU-CP
                                    S800-RSU cable incl. 10-pole Micro Fit 3.0 plug
                                    Length of cable:   3 m
                                    Cross section:     10 x 0.5 m 2

                                    Temperature range
                                    moving state:      –5 ºC ... +70 ºC
                                    fixed state:       –30 ºC ... +80 ºC
                                    Rated voltage:     300 V
                                    Conductor resistance:  39.0 Ω/km
                                    Approvals:         S+, UL