          Protection and safety
          OVR Type 1+2 surge protective devices Single pole




 Technical features
 Type codes  OVR T1-T2  12.5-440s P  QS  OVR T1-T2 N 50-275s P QS  OVR T1-T2 N 50-440s P QS
 with auxiliary contact (TS)  OVR T1-T2  12.5-440s P  TS QS                                                            5
 Technology  Varistor  GDT  GDT
 Electrical features
 Standard  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11
 Type/test class  T1-T2/I - II  T1-T2/I - II   T1-T2/I - II
 Protected lines  1  N  N
 System network  TT (L-N) / TNS / TNC  TT (N-PE) / TNS (N-PE)  TT (N-PE) / TNS (N-PE)
 Type of current  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz
 Voltage regulation of the system network  ± 10 %  ± 20 %  ± 10 %
 Nominal system voltage Un  [V]  400  230  400
 Max. cont. operating voltage Uc  [V]  440  275  440
 Maximum impulse current Iimp (10/350)  [kA]  12.5  50  50
 Nominal discharge current In 8/20)  [kA]  20  50  50
 Maximum discharge current Imax (8/20)  [kA]  80  100  100
 Follow current interrupting rating Ifi  [kA]  -  -  -
 Voltage protection level Up at In (L-N/N-PE/L-PE)  [kV]  1.9/-/1.9  -/1.4/-  -/1.9/-
 Voltage protection level Ures at 3 kA  [kV]  0.5  -  -
 TOV (Temporary overvoltage) withstand Ut    [V]  581/  -/1200  -/1200
 (L-N: 5s./N-PE: 200ms)
 Response time  [ns]  < 25  ≤10  ≤10
 Short-circuit withstand capability Isccr  [kA]  ≤ 100  ≤100  ≤100
 Backup protection   fuse (gG)  [A]  ≤ 160  -  -
 maximum rating  circuit breaker (B or C curve) [A]  ≤ 125  -  -
 Pluggable cartridge  Yes  Yes  Yes
 Integrated  thermal disconnector  Yes   No  No
 State indicator  Yes   No  No
 Safety reserve  Yes   No  No
 Auxiliary contact  Yes (TS option)  No  No
 Installation
 Wire range (L, N, PE)  solid wire  [mm²]  2.5 … 35  2.5 … 50  2.5 … 50
 stranded wire  [mm²]  2.5 … 25  2.5 … 35  2.5 … 35
 Stripping length (L, N, PE)  [mm]  12.5  12.5  12.5
 Tightening torque (L, N, PE)  [Nm]  2.8  3.5  3.5
 Auxiliary contact (TS)
 Contacts information  1 NO - 1 NC
 Min. load  12 V DC - 10 mA
 Max. load  250 V AC - 1A
 Connection cross-section  [mm²]  6.5
 Miscellaneous characteristics
 Stocking and operating temperature  [°C]  -40 to +80  -40 to +80  -40 to +80
 Maximal Altitude  [m]  5000  5000  5000
 Degree of protection  IP20 - Indoor   IP20 - Indoor  IP20 - Indoor
 Fire resistance according to UL 94  V-0  V-0  V-0
 Dimensions
 height x width x depth  [mm]  88 x 35.6 x 76.7  88 x 17.8 x 76.7  88 x 17.8 x 76.7
 [inches] 3.46 x 1.4 x 3.02  3.46 x 0.7 x 3.02  3.46 x 0.7 x 3.02
 Dimensions with auxiliary contact (TS)
 height x width x depth  [mm]  95.8 x 35.6 x 76.7
 [inches] 3.77 x 1.4 x 3.02
 Replacement Cartridges
 Phase Product ID  OVR T1-T2  12.5-440s C  QS
 2CTB815710R5500
 Neutral Product ID  -  OVR T1-T2 N 50-275s C QS  OVR T1-T2 N 50-440s C QS
 2CTB815710R2700  2CTB815710R5600
   456   457   458   459   460   461   462   463   464   465   466