Page 460 - Din prodcuts 2020
P. 460

5/16             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 1+2 surge protective devices Single pole




                                    Technical features
                                    Type codes                               OVR T1-T2  12.5-440s P  QS  OVR T1-T2 N 50-275s P QS  OVR T1-T2 N 50-440s P QS
                                    with auxiliary contact (TS)              OVR T1-T2  12.5-440s P  TS QS
  5
                                    Technology                               Varistor               GDT                           GDT
                                    Electrical features
                                    Standard                                 IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11   IEC 61643-11/EN 61643-11
                                    Type/test class                          T1-T2/I - II           T1-T2/I - II                  T1-T2/I - II
          OVR T1-T2 25-255 P TS QS  Protected lines                          1                      N                             N
                                    System network                           TT (L-N) / TNS / TNC   TT (N-PE) / TNS (N-PE)        TT (N-PE) / TNS (N-PE)
                                    Type of current                          AC 47-63 Hz            AC 47-63 Hz                   AC 47-63 Hz
                                    Voltage regulation of the system network  ± 10 %                ± 20 %                        ± 10 %
                                    Nominal system voltage Un          [V]   400                    230                           400
                                    Max. cont. operating voltage Uc    [V]   440                    275                           440
                                    Maximum impulse current Iimp (10/350)  [kA]  12.5               50                            50
                                    Nominal discharge current In 8/20)  [kA]  20                    50                            50
                                    Maximum discharge current Imax (8/20)  [kA]  80                 100                           100
                                    Follow current interrupting rating Ifi  [kA]  -                 -                             -
                                    Voltage protection level Up at In (L-N/N-PE/L-PE)  [kV]  1.9/-/1.9  -/1.4/-                   -/1.9/-
                                    Voltage protection level Ures at 3 kA  [kV]  0.5                -                             -
                                    TOV (Temporary overvoltage) withstand Ut    [V]  581/           -/1200                        -/1200
                                    (L-N: 5s./N-PE: 200ms)
                                    Response time                      [ns]  < 25                   ≤10                           ≤10
                                    Short-circuit withstand capability Isccr  [kA]  ≤ 100           ≤100                          ≤100
                                    Backup protection   fuse (gG)      [A]   ≤ 160                  -                             -
                                    maximum rating   circuit breaker (B or C curve) [A]  ≤ 125      -                             -
                                    Pluggable cartridge                      Yes                    Yes                           Yes
                                    Integrated  thermal disconnector         Yes                    No                            No
                                    State indicator                          Yes                    No                            No
                                    Safety reserve                           Yes                    No                            No
                                    Auxiliary contact                        Yes (TS option)        No                            No
                                    Installation
                                    Wire range (L, N, PE)  solid wire  [mm²]  2.5 … 35              2.5 … 50                      2.5 … 50
                                                     stranded wire     [mm²]  2.5 … 25              2.5 … 35                      2.5 … 35
                                    Stripping length (L, N, PE)        [mm]  12.5                   12.5                          12.5
                                    Tightening torque (L, N, PE)       [Nm]  2.8                    3.5                           3.5
                                    Auxiliary contact (TS)
                                    Contacts information                     1 NO - 1 NC
                                    Min. load                                12 V DC - 10 mA
                                    Max. load                                250 V AC - 1A
                                    Connection cross-section           [mm²]  6.5
                                    Miscellaneous characteristics
                                    Stocking and operating temperature  [°C]  -40 to +80            -40 to +80                    -40 to +80
                                    Maximal Altitude                   [m]   5000                   5000                          5000
                                    Degree of protection                     IP20 - Indoor          IP20 - Indoor                 IP20 - Indoor
                                    Fire resistance according to UL 94       V-0                    V-0                           V-0
                                    Dimensions
                                    height x width x depth             [mm]  88 x 35.6 x 76.7       88 x 17.8 x 76.7              88 x 17.8 x 76.7
                                                                       [inches] 3.46 x 1.4 x 3.02   3.46 x 0.7 x 3.02             3.46 x 0.7 x 3.02
                                    Dimensions with auxiliary contact (TS)
                                    height x width x depth             [mm]  95.8 x 35.6 x 76.7
                                                                       [inches] 3.77 x 1.4 x 3.02
                                    Replacement Cartridges
                                    Phase Product ID                         OVR T1-T2  12.5-440s C  QS
                                                                             2CTB815710R5500
                                    Neutral Product ID                       -                      OVR T1-T2 N 50-275s C QS      OVR T1-T2 N 50-440s C QS
                                                                                                    2CTB815710R2700               2CTB815710R5600
   455   456   457   458   459   460   461   462   463   464   465