Page 465 - Din prodcuts 2020
P. 465

5/21




          —
          Protection and safety
          OVR Type 1+2 surge protective devices TNC 230 and 400 V networks




 Technical features
 Type codes  OVR T1-T2 3L 25-255 P QS  OVR T1-T2 3L 25-440 P QS  OVR T1-T2 3L 12.5-275s P QS  OVR T1-T2 3L 12.5-440s P QS
 with auxiliary contact (TS)  OVR T1-T2 3L 25-255 P TS QS  OVR T1-T2 3L 25-440 P TS QS  OVR T1-T2 3L 12.5-275s P TS QS  OVR T1-T2 3L 12.5-440s P TS QS  5
 Technology  Varistor                Varistor
 Electrical features
 Standard  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11
 Type/test class  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II
 Protected lines  3  3  3            3
 System network  TNC  TNC  TNC       TNC
 Type of current  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz
 Voltage regulation of the system network  ± 10 %  ± 10 %  ± 20 %  ± 10 %
 Nominal system voltage Un  [V]  230/400  400/690 TNC, 230/400 (IT)  230/400   400/690 TNC, 230/400 (IT)
 Max. cont. operating voltage Uc  [V]  255  440  275  440
 Maximum impulse current Iimp (10/350)  [kA]  25  25  12.5  12.5
 Max.Imp current Tot Iimp (10/350)  [kA]  -  -  37.5  37.5
 Nominal discharge current In (8/20)  [kA]  25  25  20  20
 Maximum discharge current Imax (8/20)  [kA]  70  70  80  80
 Follow current interrupting rating Ifi  [kA]  100  15  -  -
 Voltage protection level Up at In (L-N..)  [kV]  ≤ 1.5/-/1.5  ≤ 2.5/-/1.5  -/-/1.4  -/-/2
 Voltage protection level Ures at 3 kA  [kV]  -  0.5  0.8
 TOV (Temporary overvoltage) withstand Ut   [V]  337/–  581 / –  337/–  581/–
 (L-N..)
 Response time  [ns]  ≤ 100  ≤ 100  ≤ 25  ≤ 25
 Short-circuit withstand capability Isccr  [kA]  100  15  100  100
 Backup protection   fuse (gG)  [A]  ≤ 315  ≤ 315  ≤ 160  ≤ 160
 maximum rating  circuit breaker (B or C)  [A]  –  –  ≤ 125  ≤ 125
 Pluggable cartridge  Yes  Yes  Yes  Yes
 Integrated  thermal disconnector  Yes  Yes  Yes   Yes
 State indicator  Yes  Yes  Yes      Yes
 Safety reserve  No  No  Yes         Yes
 Auxiliary contact  Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)
 Installation
 Wire range    solid wire  [mm²]  25 … 50  25 … 50  2.5 … 35  2.5 … 35
 (L, N, PE)  stranded wire  [mm²]  25 … 35  25 … 35  2.5 … 25  2.5 … 25
 Stripping length (L, N, PE)  [mm]  15  15  12.5  12.5
 Tightening torque (L, N, PE)  [Nm]  2.5  2.5  2.8  2.8
 Auxiliary contact (TS)
 Contacts information  1 NO - 1 NC  1 NO - 1  NC  1 NO - 1  NC  1 NO - 1  NC
 Min. load  12 DC - 10 mA  12 DC - 10 mA  12 DC - 10 mA  12 DC - 10 mA
 Max. load  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A
 Connection cross-section  [mm²]  0.5 ... 1.5  0.5 ... 1.5  1.5  1.5
 Miscellaneous characteristics
 Stocking and operating temperature  [°C]  -40 to +80  -40 to +80  -40 to +80  -40 to +80
 Maximal Altitude  [m]  2000  2000  5000  5000
 Degree of protection  IP20  IP20  IP20 - Indoor   IP20 - Indoor
 Fire resistance according to UL 94  V-0  V-0  V-0  V-0
 Dimensions
 height x width x depth  [mm]  108.1 × 108 × 86.3  108.1 × 108 × 86.3  88 x 53.4 x 76.7  88 x 106.8 x 76.7
 [inches] 4.25 x 1.41 x 3.38  4.25 x 1.41 x 3.38  3.46 x 2.1 x 3.02  3.46 x 4.2 x 3.02
 Dimensions with auxiliary contact (TS)
 height x width x depth  [mm]  109.2 × 108 × 86.3  109.2 × 108 × 86.3  95.8 x 53.4 x 76.7  95.8 x 106.8 x 76.7
 [inches] 4.29 x 1.41 x 3.38  4.29 x 1.41 x 3.38  3.77 x 2.1 x 3.02  3.77 x 4.2 x 3.02
 Replacement Cartridges
 Phase Product ID  OVR T1-T2 25-255 C QS  OVR T1-T2 25-255 C QS  OVR T1-T2  12.5-275s C  QS   OVR T1-T2  12.5-440s C  QS
 2CTB825101R8000  2CTB825101R8000  2CTB815710R2600  2CTB815710R5500
   460   461   462   463   464   465   466   467   468   469   470