Page 467 - Din prodcuts 2020
P. 467

5/23




          —
          Protection and safety
          OVR Type 1+2 surge protective devices TNS/TT 230 1Ph+N and 3Ph+N networks




 Technical features
 Type codes  OVR T1-T2 1N 25-255 P QS  OVR T1-T2 1N 12.5-275s P QS  OVR T1-T2 4L 25-255 P QS  OVR T1-T2 3N 25-255 P QS  OVR T1-T2 3N 12.5-275s P QS  OVR T1-T2 4L 12.5-275s P QS
 with auxiliary contact (TS)  OVR T1-T2 1N 25-255 P TS QS  OVR T1-T2 1N 12.5-275s P TS QS  OVR T1-T2 4L 25-255 P TS QS  OVR T1-T2 3N 25-255 P TS QS  OVR T1-T2 3N 12.5-275s P TS QS  OVR T1-T2 4L 12.5-275s P  TS QS  5
 Technology  Varistor + GDT                                  Varistor + GDT            Varistor
 Electrical features
 Standard  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11   IEC 61643-11/EN 61643-11    IEC 61643-11/EN 61643-11   IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11
 Type/test class  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II  T1-T2/I - II
 Protected lines  1+1  1+1  4      3+1                       3+1                       3+N
 System network  TNS / TT   TNS / TT  TNS  TNS / TT          TNS / TT                  TNS
 Type of current  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz      AC 47-63 Hz
 Voltage regulation of the system network  ± 20 %            ± 20 %                    ± 20 %
 Nominal system voltage Un  [V]  230  230  230 / 400  230 / 400  230/400               230/400
 Max. cont. operating voltage Uc  [V]  255  275  255  255    275                       275
 Maximum impulse cu rrent Iimp (10/350)  [kA]  25  12.5  25  25  12.5                  12.5
 Max.Imp current Tot Iimp (10/350)  [kA]  50  25  25  25     50                        50
 Nominal discharge current In (8/20)  [kA]  25  20  70  70   20                        20
 Maximal discharge current Imax (8/20) kA  [kA]  70  80      80                        80
 Follow current interrupting rating Ifi  [kA]  100  100  100                           -
 Voltage protection level Up at In (L-N/N-PE/L-PE)  [kV]  337 / 1200  1.4/1.4/1.5  ≤ 1.5  ≤ 1.5  1.4/1.4/1.5  2.8/1.4/1.4
 Voltage protection level Ures at 3 kA  [kV]  0.5            0.5                       0.5
 TOV (Temporary overvoltage) withstand Ut    [V]  337/1200  337 / –  337 / 1200  337/1200  337/
 (L-N: 5s./N-PE: 200ms)
 Response time  [ns]  ≤ 100  ≤ 25  ≤ 100  ≤ 100              ≤ 25                      ≤ 25
 Short-circuit withstand capability Isccr  [kA]  100  100  100  100  100               100
 Backup protection   fuse (gG)  [A]  ≤ 315  ≤ 160  ≤ 315  ≤ 315  ≤ 160                 ≤ 160
 maximum rating  circuit breaker (B or C curve)  [A]  -  ≤ 125  -  -  ≤ 125            ≤ 125
 Pluggable cartridge  Yes  Yes  Yes  Yes                     Yes                       Yes
 Integrated  thermal disconnector  Yes  Yes   Yes  Yes       Yes                       Yes
 State indicator  Yes  Yes   Yes    Yes                      Yes                       Yes
 Safety reserve  No  Yes   No       No                       Yes                       Yes
 Auxiliary contact  Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)
 Installation
 Wire range (L, N, PE)  solid wire  [mm²]  25 … 50  2.5 … 35  25 … 50  25 … 50  2.5 … 35  2.5 … 35
 stranded wire  [mm²]  25 … 35  2.5 … 25  25 … 35  25 … 35   2.5 … 25                  2.5 … 25
 Stripping length (L, N, PE)  [mm]  15  12.5  15  15         12.5                      12.5
 Tightening torque (L, N, PE)  [Nm]  2.5  2.8  2.5  2.5      2.8                       2.8
 Auxiliary contact (TS)
 Contacts information  1 NO - 1 NC  1 NO - 1 NC  1 NO - 1 NC  1 NO - 1 NC  1 NO - 1 NC  1 NO - 1 NC
 Min. load  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC  - 10 mA
 Max. load  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A  250 V AC - 1A
 Connection cross-section  [mm²]  0.5 … 1.5  1.5  0.5 … 1.5  0.5 … 1.5  1.5            1.5
 Miscellaneous characteristics
 Stocking and operating temperature  [°C]  -40 to +80  -40 to +80  -40 to +80  -40 to +80  -40 to +80  -40 to +80
 Maximal Altitude  [m]  2000  5000  2000  2000               5000                      5000
 Degree of protection  IP20  IP20 - Indoor   IP20  IP20      IP20 - Indoor             IP20 - Indoor
 Fire resistance according to UL 94  V-0  V-0  V-0  V-0      V-0                       V-0
 Dimensions
 height x width x depth  [mm]  108.1 × 72 × 86.3  88 x 35.6 x 76.7  108.1 × 144 × 86.3  108.1 × 144 × 86.3  88 x 71.2 x 76.7  88 x 71.2 x 76.7
 [in]  4.25 x 2.83 x 3.38  3.46 x 1.4 x 3.02  4.25 x 5.66 x 3.38  4.25 x 5.66 x 3.38  3.46 x 2.8 x 3.02  3.46 x 2.8 x 3.02
 Dimensions with auxiliary contact (TS)
 height x width x depth  [mm]  108.1 × 72 × 86.3  95.8 x 35.6 x 76.7  109.2 × 144 × 86.3  109.2 × 144 × 86.3  95.8 x 71.2 x 76.7  95.8 x 71.2 x 76.7
 [in]  4.25 x 2.83 x 3.38  3.46 x 1.4 x 3.02  4.29 x 5.66 x 3.38  4.29 x 5.66 x 3.38  3.77 x 2.8 x 3.02  3.77 x 2.8 x 3.02
 Replacement Cartridges
 Phase Product ID  OVR T1-T2 25-255 C QS   OVR T1-T2  12.5-275s C  QS   OVR T1-T2 25-255 C QS   OVR T1-T2 25-440 C QS  OVR T1-T2  12.5-275s C  QS   OVR T1-T2  12.5-275s C  QS
 2CTB825101R8000  2CTB815710R2600  2CTB825101R8000  2CTB825101R8100  2CTB815710R2600   2CTB815710R2600
 Neutral Product ID  OVR T1-T2 N 100-255 C QS   OVR T1-T2 N 50-275s C QS  OVR T1-T2 N 100-255 C QS  OVR T1-T2 N 100-400 C QS  OVR T1-T2 N 50-275s C QS
 2CTB825101R8200  2CTB815710R2700  2CTB825101R8200  2CTB825101R8300  2CTB815710R2700
   462   463   464   465   466   467   468   469   470   471   472