5/24             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 1+2 surge protective devices TNS/TT 400 V 1Ph+N and 3Ph+N networks




                                    Technical features
                                    Type codes                                OVR T1-T2 1N 12.5-440s P QS                       OVR T1-T2 3N 12.5-440s P QS  OVR T1-T2 4L 12.5-440s P QS
                                    with auxiliary contact (TS)               OVR T1-T2 1N 12.5-440s P TS QS                    OVR T1-T2 3N 12.5-440s P TS QS  OVR T1-T2 4L 12.5-440s P TS QS
  5
                                    Technology                                Varistor + GDT                                    Varistor + GDT               Varistor
                                    Electrical features
                                    Standard                                  IEC 61643-11/EN 61643-11                          IEC 61643-11/EN 61643-11     IEC 61643-11/EN 61643-11
                                    Type/test class                           T1-T2/I - II                                      T1-T2/I - II                 T1-T2/I - II
                                    Protected lines                           1+1                                               3+1                          4
          OVR T1-T2 1N              System network                            TT- TNS                                           TT- TNS                      TNS
          12.5-440s P TS QS
                                    Type of current                           AC 47-63 Hz                                       AC 47-63 Hz                  AC 47-63 Hz
                                    Voltage regulation of the system network  ± 10 %                                            ± 10 %                       ± 10 %
                                    Nominal system voltage Un            [V]  400                                               400/690                      400/690
                                    Max. cont. operating voltage Uc      [V]  440                                               440                          440
                                    Maximum impulse current Iimp (10/350)  [kA]  12.5                                           12.5                         12.5
                                    Max.Imp current Tot Iimp (10/350)    [kA]  25                                               50                           50
                                    Nominal discharge current In (8/20)  [kA]  20                                               20                           20
                                    Maximal discharge current Imax (8/20) kA  [kA]  80                                          80                           80
                                    Follow current interrupting rating Ifi  [kA]
                                    Voltage protection level Up at In (L-N/N-PE/L-PE)  [kV]  1.9/1.9/2                          1.9/1.9/2                    3.8/1.9/1.9
                                    Voltage protection level Ures at 3 kA  [kV]  0.8                                            0.8                          0.8
                                    TOV (Temporary overvoltage) withstand Ut    [V]  581/1200                                   581/1200                     581/
                                    (L-N: 5s./N-PE: 200ms)
                                    Response time                        [ns]  ≤ 25                                             ≤ 25                         ≤ 25
                                    Short-circuit withstand capability Isccr  [kA]  100                                         100                          100
                                    Backup protection   fuse (gG)        [A]  ≤ 160                                             ≤ 160                        ≤ 160
                                    maximum rating  circuit breaker      [A]  ≤ 125                                             ≤ 125                        ≤ 125
                                                    (B or C curve)
                                    Pluggable cartridge                       Yes                                               Yes                          Yes
                                    Integrated  thermal disconnector          Yes                                               Yes                          Yes
                                    State indicator                           Yes                                               Yes                          Yes
                                    Safety reserve                            Yes                                               Yes                          Yes
                                    Auxiliary contact                         Yes (TS option)                                   Yes (TS option)              Yes (TS option)
                                    Installation
                                    Wire range (L, N, PE)  solid wire    [mm²] 2.5 … 35                                         2.5 … 35                     2.5 … 35
                                                    stranded wire        [mm²] 2.5 … 25                                         2.5 … 25                     2.5 … 25
                                    Stripping length (L, N, PE)          [mm]  12.5                                             12.5                         12.5
                                    Tightening torque (L, N, PE)         [Nm]  2.8                                              2.8                          2.8
                                    Auxiliary contact (TS)
                                    Contacts information                      1 NO - 1 NC                                       1 NO - 1 NC                  1 NO - 1 NC
                                    Min. load                                 12 V DC - 10 mA                                   12 V DC - 10 mA              12 V DC - 10 mA
                                    Max. load                                 250 V AC - 1 A                                    250 V AC - 1 A               250 V AC - 1 A
                                    Connection cross-section             [mm²] 1.5                                              1.5                          1.5
                                    Miscellaneous characteristics
                                    Stocking and operating temperature   [°C]  -40 to +80                                       -40 to +80                   -40 to +80
                                    Maximal Altitude                     [m]  5000                                              5000                         5000
                                    Degree of protection                      IP20 - Indoor                                     IP20 - Indoor                IP20 - Indoor
                                    Fire resistance according to UL 94        V-0                                               V-0                          V-0
                                    Dimensions
                                    height x width x depth               [mm]  88 x 53.4 x 76.7                                 88 x 124.6 x 76.7            88 x 142.4 x 76.7
                                                                         [in]  3.46 x 2.1 x 3.02                                3.46 x 4.91 x 3.02           3.46 x 5.61 x 3.02
                                    Dimensions with auxiliary contact (TS)
                                    height x width x depth               [mm]  95.8 x 53.4 x 76.7                               95.8 x 124.6 x 76.7          95.8 x 142.4 x 76.7
                                                                         [in]  3.77 x 2.1 x 3.02                                3.77 x 4.91 x 3.02           3.77 x 5.61 x 3.02
                                    Replacement Cartridges
                                    Phase Product ID                          OVR T1-T2  12.5-440s C QS                         OVR T1-T2  12.5-440s C QS    OVR T1-T2  12.5-440s C QS
                                                                              2CTB815710R5500                                   2CTB815710R5500              2CTB815710R5500
                                    Neutral Product ID                        OVR T1-T2 N 50-440s C QS                          OVR T1-T2 N 50-440s C QS
                                                                              2CTB815710R5600                                   2CTB815710R5600