5/28             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 2 surge protective devices for 57 V networks




          Technical features
          Types                                      OVR T2 20-75 P               OVR T2 2 20-75 P
          with auxiliary contact (TS)                OVR T2 20-75 P TS            OVR T2 2 20-75 P TS
  5
          Technology                                 Varistor                     Varistor
          Electrical features
          Standard                                   IEC 61643-1/EN 61643-11      IEC 61643-1/EN 61643-11
          Type/test class                            T2/II                        T2/II
          Protected lines                            1                            2
          Types of networks                          TT-TNS-TNC                   TT-TNS-TNC
          Type of current                            AC - DC                      AC - DC
          Nominal AC voltage Un                [V]   57                           57
          Max. cont. operating AC voltage Uc   [V]   75                           75
          Maximum discharge current Imax (8/20)  [kA]  20                         20
          Nominal discharge current In (8/20)  [kA]  5                            5
          Voltage protection level Up at In    [kV]  0.3                          0.3
          Voltage protection level Up at 3 kA  [kV]  0.25                         0.25
          TOV (Temporary overvoltage) withstand Ut   [V]  75/-                    75/-
          (L-N: 5s/N-PE: 200ms)
          Response time                        [ns]  ≤ 25                         ≤ 25
          Residual current IPE                 [μA]  ≤110                         ≤10
          Short-circuit withstand capability Isccr  [kA]  50                      50
          Backup protection   fuse (gG)        [A]   ≤ 16                         ≤ 16
          maximum rating      circuit breaker   [A]  ≤ 16                         ≤ 16
                              (B or C curve)
          Pluggable cartridge                        Yes                          Yes
          Integrated  thermal disconnector           Yes                          Yes
          State indicator                            Yes                          Yes
          Safety reserve                             No                           No
          Auxiliary contact (TS)                     Yes (TS option)              Yes (TS option)
          Installation
          Wire range (L, N, PE)  solid wire    [mm²]  2.5 … 25                    2.5 … 25
                              stranded wire    [mm²]  2.5 … 16                    2.5 … 16
          Stripping length (L, N, PE)          [mm]  12.5                         12.5
          Tightening torque (L, N, PE)         [Nm]  2.5                          2.5
          Auxiliary contact (TS)
          Contact complement                         1 NO - 1 NC                  1 NO - 1 NC
          Min. load                                  12 V DC - 10 mA              12 V DC - 10 mA
          Max. load                                  250 V AC - 1 A               250 V AC - 1 A
          Connection cross-section             [mm²]  1.5                         1.5
          Miscellanous characteristics
          Stocking and operating temperature   [°C]  -40 to +80                   -40 to +80
          Maximal Altitude                     [m]   5000                         5000
          Degree of protection                       IP 20                        IP 20
          Fire resistance according to UL 94         V-0                          V-0
          Dimensions
          height x width x depth               [mm]  88 x 17.8 x 65               88 x 35.6 x 65
                                               [in]  3.46 x 0.7 x 2.56            3.46 x 1.4 x 2.56
          Dimensions with auxilary contact (TS)
          height x width x depth               [mm]  96 x 17.8 x 65               96 x 35.6 x 65
                                               [in]  3.78 x 0.7 x 2.56            3.78 x 1.4 x 2.56
          Replacement Cartridges
          Phase Product ID                           OVR T2 20-75 C               OVR T2 20-75 C
                                                     2CTB803854R1400              2CTB803854R1400