Page 474 - Din prodcuts 2020
P. 474

5/30             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          OVR Type 2 surge protective devices non pluggable




          Technical features
          Types                                      OVR T2 20-275                OVR T2 40-275
          with auxiliary contact (TS)                -                            -
  5
          Technology                                 Varistor                     Varistor
          Electrical features
          Standard                                   IEC 61643-11/EN 61643-11     IEC 61643-11/EN 61643-11
          Type/test class                            T2/II                        T2/II
          Protected lines                            1                            1
          Types of networks                          TT(L-N)-TNS-TNC              TT(L-N)-TNS-TNC
          Type of current                            AC 47-63 Hz                  AC 47-63 Hz
          Voltage regulation of the system network   ± 20 %                       ± 20 %
          Nominal AC voltage Un                [V]   230                          230
          Max. cont. operating AC voltage Uc   [V]   275                          275
          Maximum discharge current Imax (8/20)  [kA]  20                         40
          Nominal discharge current In (8/20)  [kA]  5                            20
          Voltage protection level Up at In    [kV]  1                            1.4
          Voltage protection level Up at 3 kA  [kV]  0.9                          0.9
          TOV (Temporary overvoltage) withstand Ut   [V]  337/-                   337/-
          (L-N: 5s/N-PE: 200ms)
          Response time                        [ns]  ≤ 25                         ≤ 25
          Residual current IPE                 [μA]  ≤110                         ≤110
          Short-circuit withstand capability Isccr  [kA]  50                      50
          Backup protection   fuse (gG)        [A]   ≤ 50                         ≤ 50
          maximum rating      circuit breaker   [A]  ≤ 50                         ≤ 50
                              (B or C curve)
          Pluggable cartridge                        No                           No
          Integrated  thermal disconnector           Yes                          Yes
          State indicator                            Yes                          Yes
          Safety reserve                             No                           No
          Auxiliary contact (TS)                     No                           No
          Installation
          Wire range (L, N, PE)  solid wire    [mm²]  2.5…25                      2.5…25
                              stranded wire    [mm²]  2.5…16                      2.5…16
          Stripping length (L, N, PE)          [mm]  12.2                         12.2
          Tightening torque (L, N, PE)         [Nm]  2.5                          2.5
          Auxiliary contact (TS)
          Contact complement                         –                            –
          Min. load                                  –                            –
          Max. load                                  –                            –
          Connection cross-section             [mm²]  –                           –
          Miscellanous characteristics
          Stocking and operating temperature   [°C]  -40 to +80                   -40 to +80
          Maximal Altitude                     [m]   2000                         2000
          Degree of protection                       IP 20                        IP 20
          Fire resistance according to UL 94         V-0                          V-0
          Dimensions
          height x width x depth               [mm]  85 x 17.8 x 64.8             85 x 17.8 x 64.8
                                               [in]  3.35 x 0.70 x 2.55           3.35 x 0.70 x 2.55
   469   470   471   472   473   474   475   476   477   478   479