Page 477 - Din prodcuts 2020
P. 477

5/33




          —
          Protection and safety
          OVR Type 2 pluggable QuickSafe® surge protective devices Single pole
          230 V networks


 Technical features
 Types  OVR T2 40-275 P QS  OVR T2 40-275s P QS  OVR T2 40-350 P QS  OVR T2  80-275s P  QS  OVR T2-T3 N 80-275 P QS  OVR T2 N 80-350 P QS  OVR T2 N 80-275s P QS
 with auxiliary contact (TS)  OVR T2 40-275 P TS QS  OVR T2 40-275s P TS QS  OVR T2 40-350 P TS QS  OVR T2 80-275s P TS QS  5
 Technology  Varistor  Varistor  Varistor  Varistor  GDT               GDT                  GDT
 Electrical features
 Standard  IEC 61643-11/EN 61643-11   IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11  IEC 61643-11/EN 61643-11
 Type/test class  T2/II  T2/II  T2/II  T2/II       T2-T3/II-III        T2/II                T2
 Protected lines  1  1  1     1                    1                   1                    1
 System network  TT(L-N)-TNS-TNC  TT(L-N)-TNS-TNC  TT(L-N)-TNS-TNC  TT(L-N)-TNS-TNC  TT (N-PE)-TNS(N-PE)  TT (N-PE)-TNS(N-PE)  TT(N-PE)-TNS(N-PE)
 Type of current  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz  AC 47-63 Hz
 Voltage regulation of the system network  ± 20 %  ± 20 %  ± 50 %  ± 20 %  ± 20 %  ± 50 %    ± 20 %
 Nominal system voltage Un  [V]  230  230  230  230  230               230                  230
 Max. cont. operating voltage Uc  [V]  275  275  350  275  275         350                  275
 Nominal dc voltage Un dc L-PE  [V dc]  320  -  375  -  -              -                    -
 Max. dc. cont. operating voltage Ucdc L-PE  [V dc]  355  -  415  -  -  -                   -
 Maximum discharge current Imax (8/20)  [kA]  40  40  40  80  80       80                   80
 Maximum impulse current Iimp (10/350)  [kA]  2  2  2  6.25  2         2                    6.25
 Nominal discharge current In (8/20)  [kA]  20  20  20  20  30         30                   30
 Voltage protection level Up at In (L-N/N-PE/L-PE)  [kV]  1.25/-/1.25  1.4/-/1.4  1.5/-/1.5  1.4/-/1.4  -/1.4/-  -/1.4/-  -/1.4/-
 Voltage protection level Ures at 3kA (L-N)  [kV]  0.8  0.5  1  0.5  -  -                   -
 Voltage protection level Ures at 5kA (L-N)  [kV]  0.85  0.7  1.05  0.7  -  -               -
 Voltage protection level Ures at 10kA (L-N)  [kV]  1  0.9  1.2  0.9  -  -                  -
 TOV (Temporary overvoltage) withstand Ut (L-N: 5s./N-PE: 200ms)  [V]  337/-  337/-  455/-  337/  -/1200  -/1200  -/1200
 Response time  [ns]  ≤ 25  ≤ 25  ≤ 25  ≤ 25       < 25                < 25                  < 25
 Short-circuit withstand capability Isccr  [kA]  100  100  100  100  -  -                   100
 Backup protection maximum rating  fuse (gG)  [A]  ≤ 125  ≤ 160  ≤ 125  ≤ 160  ≤ 125  ≤ 125  ≤160
 circuit breaker (B or C curve)  [A]  ≤ 125  ≤ 125  ≤ 125  ≤ 125  ≤ 125  ≤ 125              ≤125
 Pluggable cartridge  Yes  Yes  Yes  Yes           Yes                 Yes                  Yes
 Integrated QuickSafe® technology  Yes  Yes  Yes  Yes  -               -                    -
 State indicator  Yes  Yes  Yes  Yes               No                  No                   No
 Safety reserve  No  Yes  No  Yes                  No                  No                   No
 Auxiliary contact  Yes (TS option)  Yes (TS option)  Yes (TS option)  Yes (TS option)  No  No  No
 Installation
 Wire range (L, N, PE)  solid wire  [mm²]  2.5 … 35  2.5 … 35  2.5 … 35  2.5 … 35  2.5 … 35  2.5 … 35  2.5 … 35
 stranded wire  [mm²]  2.5 … 25  2.5 … 25  2.5 … 25  2.5 … 25  2.5 … 25  2.5 … 25           2.5 … 25
 Stripping length (L, N, PE)  [mm]  12.5  12.5  12.5  12.5  12.5       12.5                 15
 Tightening torque (L, N, PE)  [Nm]  2.8  2.8  2.8  2.8  2.8           2.8                  3.5
 Auxiliary contact (TS)
 Contacts information  1 NO - 1 NC  1 NO - 1 NC  1 NO- 1 NC  1 NO- 1 NC  -  -               -
 Min. load  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC - 10 mA  12 V DC - 10 mA  -  -        -
 Max. load  250 V AC - 1 A  250 V AC - 1 A  250 V AC - 1 A  250 V AC - 1 A  -  -            -
 Connection cross-section  [mm²]  1.5  1.5  1.5  1.5  -                -                    -
 Miscellanous characteristics
 Stocking and operating temperature  [°C]  -40 to +80  -40 to +80  -40 to +80  -40 to +80  -40 to +80  -40 to +80  -40 to +80
 Maximal Altitude  [m]  5000  5000  5000  5000     5000                5000                 5000
 Degree of protection  IP 20  IP 20  IP 20  IP 20 - Indoor   IP 20 - Indoor   IP 20 - Indoor    IP 20 - Indoor
 Fire resistance according to UL 94  V0  V0  V0  V-0  V-0              V-0                  V0
 Dimensions
 height x width x depth  [mm]  88 x 17.8 x 65.3  88 x 17.8 x 76.7  88 x 17.8 x 65.3  88 x 17.8 x 76.7  88 x 17.8 x 65.3  88 x 17.8 x 65.3  88 x 17.8 x 76.7
 [inches]  3.46 x 0.7 x 2.57  3.46 x 0.7 x 3.02  3.46 x 0.7 x 2.57  3.46 x 0.7 x 3.02  3.46 x 0.7 x 3.02  3.46 x 0.7 x 3.02  3.45 x 0.7 x 3.02
 With Auxiliary Contact (TS)
 height x width x depth  [mm]  95.8 x 17.8 x 65.3  95.8 x 17.8 x 76.7  95.8 x 17.8 x 65.3  95.8 x 17.8 x 76.7  -  -  -
 [inches]  3.77 x 0.7 x 2.57  3.77 x 0.7 x 3.02  3.77 x 0.7 x 2.57  3.77 x 0.7 x 3.02  -  -  -
 Replacement Cartridges
 Phase Product ID  OVR T2 40-275 C QS   OVR T2 40-275s C QS   OVR T2 40-350 C QS   OVR T2 80-275s C QS   -  -  -
 2CTB803876R1000  2CTB815704R2600  2CTB803886R1000  2CTB815708R2600
 Neutral Product ID  -  -  -  -                    OVR T2-T3 N 80-275 C QS   OVR T2 N 80-350 C QS   OVR T2 N 80-275s C QS
                                                   2CTB803876R0000     2CTB803886R0000      2CTB815708R2800