Page 548 - Din prodcuts 2020
P. 548

5/104            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          Data & signal protection
          OVR SL Series






  5






                                            Combined Category D, C, B tested protector (to BS EN 61643) suitable for
                                            twisted pair signalling applications which require either a lower in-line
                                            resistance, an increased current and/or higher bandwidth. Also suitable for
                                            DC power applications less than 0.75 Amps. Available for working voltages of up
                                            to 6, 15, 30, 50 and 110 Volts. For use at boundaries up to LPZ 0 to protect
                                            against flashover (typically the service entrance location) through to LPZ 3 to
                                            protect sensitive electronic equipment.
          Features & benefits
          •  Very low let-through voltage (enhanced protection to    •  High (750 mA) maximum running current
           IEC/BS EN 62305) between all lines - Full Mode protection  •  High bandwidth enables higher frequency (high traffic or
          •  Full Mode design capable of handling partial lightning   bit rate) data communications
           currents as well as allowing continual operation of   •  Screen terminal enables easy connection of cable screen
           protected equipment                                 to earth
          •  Repeated protection in lightning intense environments  •  Suitable for earthed or isolated screen systems - add/I
          •  Ultra slim 7 mm width ideal for compact protection of   suffix to part number for versions that require isolated
           large numbers of lines (e.g. process control installations)  screens - e.g. OVR SL30/I
          •  Optional LED status indication versions available for low   •  Built-in innovative DIN rail foot with locking feature for
           current DC power applications - add L suffix to part   simple positioning and clip-on mounting to top hat DIN rails
                                                                    2
           number - e.g. OVR SL30L                            •  4 mm  terminals allow for larger cross section wiring,
          •  Two stage removable protection module with simple quick   stranded wires terminated with ferrules or fitting two
           release mechanism allowing partial removal for easy line   wires into a single terminal
           commissioning and maintenance as well as full removal for   •  Convenient earthing through DIN foot and/or earth terminal
           protection replacement                             •  Very low (1 Ω) in-line resistance allows resistance critical
          •  Strong, flame retardant, polycarbonate housing    applications (e.g. alarm loops) to be protected


          Application                                         Installation
          Use these protectors where installation space is at   Connect in series with the data communication or signal
          a premium and large numbers of lines require protection   line either near where it enters or leaves the building or
          (e.g. process control, high speed digital communication   close to the equipment being protected (e.g. within its
          equipment or systems with long signal lines).       control panel).
                                                              Either way, it must be very close to the system’s earth
                                                              star point. Install protectors either within an existing
                                                              cabinet/cubicle or in a separate enclosure.


          Accessories                                                    LINE     Surge Protective Device  CLEAN
                                                                                  7TCA085400R0366
          Replacement modules:      OVR SL/I/B                                    Nominal voltage  30V
                                                                                  Max working voltage, U c 36.7V
                                                                                  Current rating  750mA 1. 1.0Ω 0 Ω
                                                                                  In-line resistance
          OVR SLXX/M                Base replacement with isolated     1          Max surge current  20kA 63V  3
                                                                                  Let-through voltage, U p
          Standard module replacement where XX   screen from earth     S           Line  Wilford Road,  Clean  S
                                                                                   Nottingham,
                                                                                   NG2 1EB, UK
          is voltage rating (06, 15, 30, 50 or 110)
          OVR SLXXL/M               Weatherproof enclosure:            2                         4
          LED module replacement where   OVR WBX SLQ
          XX is voltage rating, as above
          OVR SL/B
          Base replacement (common for                                 From line        To equipment
          standard and LED modules)
                                                                                  Earth
          NOTE: The OVR SL ‘Slim Line’ Series is also available for protection of 3-wire, RS 485 and RTD applications (OVR SL/3W, OVR SL RS485 & OVR SL RTD).
          The OVR SL X Series has approvals for use in hazardous areas. For telecommunication applications use OVR SLTN Series.
   543   544   545   546   547   548   549   550   551   552   553