Page 553 - Din prodcuts 2020
P. 553

5/109




          —
          Protection and safety
          Data & signal protection
          OVR D Series


          OVR D Series - Technical specification
          Electrical specification      OVR 06D        OVR 15D       OVR 30D       OVR 50D        OVR 110D
          ABB order code                7TCA085400R0288 7TCA085400R0349 7TCA085400R0351 7TCA085400R0352 7TCA085400R0347  5
          Nominal voltage  (1)          6 V            15 V          30 V          50 V           110 V
          Maximum working voltage Uc (RMS/DC)  (2)  5 V/7.79 V   13 V/19 V   26 V/37.1 V   41 V/58 V   93 V/132 V
          Current rating (signal)       300 mA
          In-line resistance (per line ±10%)  9.4 Ω    9.4 Ω         9.4 Ω         9.4 Ω          9.4 Ω
          Bandwidth (-3 dB 50 Ω system)  800 kHz       2.5 MHz       4 MHz         6 MHz          9 MHz
          Transient specification       OVR 06D        OVR 15D       OVR 30D       OVR 50D        OVR 110D
          Let-through voltage (all conductors)(3) Up
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to    12.0 V   25.0 V   44.0 V      78.0 V         155 V
          BS EN/EN/IEC 61643-21
          C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to   11.5 V   24.5 V   43.5 V    76.0 V         150 V
          BS EN/EN/IEC 61643-21
          B2 test 4 kV 10/700 μs to BS EN/EN/   10.0 V   23.0 V      42.5 V        73.0 V         145 V
          IEC 61643-21
          5 kV, 10/700 μs  (4)          10.5 V         23.8 V        43.4 V        74.9 V         150 V
          Maximum surge current
          D1 test 10/350 μs   –  Per signal wire  2.5 kA
          to BS EN/EN/IEC   –  Per pair  5 kA
          61643-21
          8/20 μs to ITU-T   –  Per signal wire  10 kA
          K.45:2003, IEEE   –  Per pair  20 kA
          C62.41.2:2002
          Mechanical specification      OVR 06D        OVR 15D       OVR 30D       OVR 50D        OVR 110D
          Temperature range             -40 to +80 °C
          Connection type               Screw terminal - maximum torque 0.5 Nm
          Conductor size (stranded)     2.5 mm 2
          Earth connection              M6 stud
          Case material                 FR Polymer UL-94 V-0
          Weight         –  Unit        0.08 kg
                         –  Packaged (per 10) 0.85 kg
          Dimensions                    See diagram below






                                                                                                             54 mm
                                                                                 38 mm
                                                                                               105 mm
                                                                                              M4 clearance

                                                                                               120 mm
                                                                                 19 mm
                                                                                               109 mm
                                                                                              M4 clearance
          (1)   Nominal voltage (RMS/DC or AC peak)
           measured at < 5 μA (OVR 15D, OVR 30D,
           OVR 50D, OVR 110D) and < 200 μA (OVR 06D)
          (2)   Maximum working voltage (RMS/DC or AC peak)
           measured at < 1 mA leakage (OVR 15D, OVR 30D,
           OVR 50D, OVR 110D), < 10 mA (OVR 06D)
          (3)   The maximum transient voltage let-through of the
           protector throughout the test (±10%), line to line &
           line to earth, both polarities. Response time < 10 ns
          (4)   Test to IEC 61000-4-5:2006, ITU-T (formerly
           CCITT) K.20, K.21 and K.45, Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)