6/48             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Command and signaling
          E297 Installation relay




                                    E297 Installation Relays

                                    General
                                    Overall depth                          68 mm
                                    Overall width                          1 module (18 mm)
                                    Colour                                 grey, RAL 7035
                                    Climate resistance in accordance with   IEC 60068-2-2 (dry heat)
  6
         E290                                                              IEC 60068-2-30 (humid heat)
                                                                           IEC 60068-2-1 (low temperatures)
                                    Ambient temperature                    - 25 °C to + 55 °C
                                    Storage temperature                    - 40 °C to + 70 °C
                                    Tightening torque                      1.2 - 1.5 Nm
                                    Weight                                 0.122 kg
                                    Standards                              EN 60669-1; EN 60669-2-2
                                    Approval                               VDE; EAC
                                    Power circuit
                                    Rated current In                       16 A
                                    Rated voltage Un                       250 VAC
                                    Frequency                              50-60 Hz
                                    Short circuit withstand capacity Inc   3 kA
                                    Back-up fuses (gL)                     max. 16 A
                                    Installation relay contact configurations  1NO; 2NO; 1NO+1NC
                                    Additional Power contacts 16A (attachable)  1CO; 2NO; 1NO+1NC
                                    Max. DC current per contact with 24 VDC  8 A
                                    Min. switching load                    24 V; 10 mA
                                    Bounce time                            < 3 ms
                                    Power loss in W per contact            0.50 W
                                    Rated Impulse withstand voltage Uimp   4 kV
                                    Max. lamp load
                                    Glow lamps (20 W-200 W)                3000 W
                                    Fluorescent lamps, uncorrected power factor (cos. 0.5)  1800 W
                                    Fluorescent lamps, corrected power factor   serial  3000 W
                                    (cos. 0.9)                      parallel  2500 W
                                                                    single  1800 W
                                                                    double  2500 W
                                    (see also lamp load table)
                                    Lifetime (switching cycles)
                                    Electrical (AC1 rated current load)    150,000
                                    Mechanical                             250,000




















                                    NO = normally-open contact; NC = normally-closed contact; CO = changeover contact