Page 681 - Din prodcuts 2020
P. 681

6/49




          —
          Command and signaling
          E297 Installation relay




                                    E297 Installation Relays

                                    Application categories
                                    Switching capacity   AC-1 (based on EN 60947)  16 A
                                    in accordance with  AC-5b (based on EN 60947)  5 A
                                                    AC-7a (based on EN 61095)  16 A
                                                                                                                       6
                                                    AC-7c (based on EN 61095)  5 A
                                    Connector cross-sections
                                    Main connecting terminals             solid from 1 x 1 mm2 to 1 x 10 mm2 or 2 x 2.5 mm2
                                                                          flexible from 1 x 0.75 mm2 up to 1 x 6 mm2 (Cu)
                                                                          with end ferrule or pin cable lug
                                    Control circuit
                                    Coil rated voltages Un AC/DC          8 VAC; 12 VAC; 24 VAC/24 VDC; 48 VAC/48 VDC;
                                                                          115 VAC/110 VDC; 230 VAC
                                    AC/DC ratio 3)                        1 : 1
                                    Operation limits                      +/- 10 % = 0.9 - 1.1 x Un
                                    Switching noise                       60 dB (A) (distance 1 m)
                                    Max. switching operations             15 x per min. at In 16 A
                                    Coil power loss
                                                                          AC                 DC
                                    Pick up                               < 2.8 VA           < 2.0 W
                                    Holding                               < 2.6 VA           < 1.8 W


                                    Switching components for E297


                                    E298 Contact Module
                                    Max. no. attachable 2) (additional main contacts)   1 unit (attachable on the right side of the main module)
                                    Rated current In per E298 contact    16 A
                                    Rated voltage Un                     250 VAC
                                    Frequency                            50 Hz
                                    Number of contacts                   1CO; 2NO; 1NO+1NC
                                    Max. DC current per contact with 24 VDC  5 A
                                    Min. switching load                  24 V; 10 mA
                                    E299-11 Auxiliary Contacts
                                    Max. no. attachable 2) (signaling or control   1 unit (attachable on the right side of the main module)
                                    contacts)
                                    Number of contacts                   1 NO+1 NC
                                    Max. current per contact with AC     5.0 A
                                    Max. current per contact with 24 VDC   5.0 A



















                                    NO = normally-open contact; NC = normally-closed contact; CO = changeover contact
 NO = normally-open contact; NC = normally-closed contact; CO = changeover contact  2) See overview of chapter 4