Page 693 - Din prodcuts 2020
P. 693
6/61
—
Command and signaling
STD universal dimmer for phase control and reverse phase control
Technical features
Rated voltage 230 V ~ ± 10%, 50/60 Hz
Rated current STD U 2.17 A
STD E 1.83 A
Max. connected load U 500 W/VA
E 420 W/VA 6
Power extension 1 U + max. 6 E/phase = > max. 3 kVA
Min. connected load STD U 60 W/VA
STD-500 U
STD E 200 W/VA
Max. line length 100 m pushbutton cable, 2 m data line
Interference suppression CE
Ambient temperature 0 ... + 45 °C, higher temperatures reduce the power
Electronic protection against short circuit, overload, excessive temperature, automatic load
recognition, soft-OFF function optional, memory function, minimum brightness control,
visual overload indication.
Universal dimmer for phase control and reverse phase control
Universal dimmer STD-500 U and the connected power extension unit STD-420 E are
suitable for the brightness control of:
STD-420 E • glow lamps
• 230 V halogen glow lamps
• lv halogen glow lamps with conventional transformer (phase control)
• electronic transformers for lv halogen glow lamps (reverse phase control) e.g.:
ABB ETR-70-230, 105-230, 150-230
The STD-500 U dimmer can be operated by one or more unlit pushbuttons (N- or
L-controlled) or via a data line:
• EIB control element SB/S
• Powernet control element PSB
Power unit STD-420 E is used to boost the connected load and is controlled exclusively by
the preset command of the STD-500 U dimmer. The parallel connection of the outputs of the
universal high-performance dimmer and the pertaining power extensions (up to 6 units; con-
nection with enclosed RJ 12 line cut to length) allow for a dimming power of 3,000 W/VA max
at one load line.
Not suitable for dimming fluorescent lamps, transformers with current monitor and
high-reactance transformers.
Contacts Power loss Bbn Order details Price Weight Pack
4016779 1 piece 1 piece unit
W EAN Type code Order code kg pc.
STD OCP, STD-OCD, high-performance dimmer 6 06692 8 STD-500 U GJB0006590A0178 1
STD-OCT extension 6 06693 5 STD-420 E GJB0006590A0179 1
rotary operation element – 06698 0 STD-OCD GJB0006590A0183 1
button operation element – 06695 9 STD-OCP GJB0006590A0181 1
timer operation element – 07056 7 STD-OCT GJB0006590A0185 1
Note: Load and control cables must not be laid in one cable