Page 693 - Din prodcuts 2020
P. 693

6/61




          —
          Command and signaling
          STD universal dimmer for phase control and reverse phase control




                                    Technical features
                                    Rated voltage             230 V ~ ± 10%, 50/60 Hz
                                    Rated current    STD U    2.17 A
                                                     STD E    1.83 A
                                    Max. connected load  U    500 W/VA
                                                     E        420 W/VA                                                 6
                                    Power extension           1 U + max. 6 E/phase = > max. 3 kVA
                                    Min. connected load  STD U  60 W/VA
          STD-500 U
                                                     STD E    200 W/VA
                                    Max. line length          100 m pushbutton cable, 2 m data line
                                    Interference suppression  CE
                                    Ambient temperature       0 ... + 45 °C, higher temperatures reduce the power

                                    Electronic protection against short circuit, overload, excessive temperature, automatic load
                                    recognition, soft-OFF function optional, memory function, minimum brightness control,
                                    visual overload indication.

                                    Universal dimmer for phase control and reverse phase control
                                    Universal dimmer STD-500 U and the connected power extension unit STD-420 E are
                                    suitable for the brightness control of:
          STD-420 E                 • glow lamps
                                    • 230 V halogen glow lamps
                                    • lv halogen glow lamps with conventional transformer (phase control)
                                    •  electronic transformers for lv halogen glow lamps (reverse phase control) e.g.:
                                     ABB ETR-70-230, 105-230, 150-230

                                    The STD-500 U dimmer can be operated by one or more unlit pushbuttons (N- or
                                    L-controlled) or via a data line:
                                    • EIB control element SB/S
                                    • Powernet control element PSB
                                    Power unit STD-420 E is used to boost the connected load and is controlled exclusively by
                                    the preset command of the STD-500 U dimmer. The parallel connection of the outputs of the
                                    universal high-performance dimmer and the pertaining power extensions (up to 6 units; con-
                                    nection with enclosed RJ 12 line cut to length) allow for a dimming power of 3,000 W/VA max
                                    at one load line.
                                    Not suitable for dimming fluorescent lamps, transformers with current monitor and
                                    high-reactance transformers.


                                    Contacts            Power loss  Bbn  Order details           Price Weight Pack
                                                                 4016779                       1 piece 1 piece unit

                                                        W        EAN    Type code  Order code        kg     pc.
          STD OCP, STD-OCD,         high-performance dimmer 6    06692 8  STD-500 U GJB0006590A0178         1
          STD-OCT                   extension           6        06693 5  STD-420 E GJB0006590A0179         1
                                    rotary operation element  –  06698 0  STD-OCD  GJB0006590A0183          1
                                    button operation element  –  06695 9  STD-OCP  GJB0006590A0181          1
                                    timer operation element  –   07056 7  STD-OCT  GJB0006590A0185          1
                                    Note: Load and control cables must not be laid in one cable