Page 698 - Din prodcuts 2020
P. 698
6/66 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Command and signaling
Control, isolating and safety transformers selection table
Selection table of products and secondary protections
Primary protection: see in Chapter 6 of Electrical installation solutions for buildings - Technical details
6
TM-C TM-S TM-I
Control Control/Safety Control/Isolating
Power Secondary 12 V 24 V 115 V 230 V 12 V 24 V 24 V 48 V 115 V 230 V
VA voltage
50 Transformer 2CSM207113R0801 2CSM207213R0801 2CSM236893R0801 2CSM204653R0801 b 2CSM204583R0801
Fuse gauge 4 A 2 A 0.4 A 0.2 A 4 A 2 A 2 A 1 A 0.4 A 0.2 A
100 Transformer 2CSM207103R0801 2CSM236933R0801 2CSM207163R0801 2CSM204643R0801 2CSM201123R0801
Fuse gauge 8 A 4 A 0.8 A 0.4 A 8 A 4 A 4 A 2 A 0.8 A 0.4 A
Breaker type S202 C8 S202 C4 S202 C1 S202 C0,5 S202 C8 S202 C4 S202 C4 S202 C2 S202 C1 S202 C0,5
160 Transformer 2CSM236853R0801 2CSM207203R0801 2CSM202073R0801 2CSM204633R0801 2CSM204533R0801
Fuse gauge 12 A 6.3 A 1.25 A 0.63 A 12 A 6,3 A 6.3 A 3.15 A 1.25 A 0.63 A
Breaker type S202 C13 S202 C8 S202 C1.6 S202 C- S202 C13 S202 C8 S202 C8 S202 C4 S202 C1.6 -
200 Transformer 2CSM236823R0801 2CSM236883R0801 2CSM260043R0801 2CSM204513R0801
Fuse gauge 16 A 8 A 1.6 A 0.8 A 16 A 8 A 1.6 A 0.8 A
Breaker type S202 C16 S202 C8 S202 C2 S202 C1 S202 C16 S202 C8 S202 C2 S202 C1
250 Transformer 2CSM207093R0801 2CSM236923R0801 2CSM260063R0801 2CSM204673R0801 2CSM204493R0801
Fuse gauge 20 A 10 A 2 A 1 A 20 A 10 A 10 A 5 A 2 A 1 A
Breaker type S202 C20 S202 C10 S202 C2 S202 C1 S202 C20 S202 C10 S202 C10 S202 C6 S202 C2 S202 C1
320 Transformer 2CSM236843R0801 2CSM236923R0801 2CSM260063R0801 2CSM204673R0801 2CSM204493R0801
Fuse gauge 25 A 12 A 2.5 A 1.25 A 25 A 12 A 12 A 6.3 A 2.5 A 1.25 A
Breaker type S202 C25 S202 C13 S202 C3 S202 C1,6 S202 C25 S202 C13 S202 C13 S202 C8 S202 C3 S202 C1,6
400 Transformer 2CSM289703R0801 2CSM207193R0801 2CSM260103R0801 2CSM204613R0801 2CSM201073R0801
Fuse gauge 32 A 16 A 3.15 A 1.6 A 32 A 16 A 16 A 8 A 3.15 A 1.6 A
Breaker type S202 C32 S202 C16 S202 C4 S202 C2 S202 C32 S202 C16 S202 C16 S202 C8 S202 C4 S202 C2
630 Transformer 2CSM236813R0801 2CSM207183R0801 2CSM260053R0801 2CSM204603R0801 2CSM204423R0801
Fuse gauge 50 A 25 A 5 A 2.5 A 50 A 25 A 25 A 12 A 5 A 2.5 A
Breaker type S202 C50 S202 C25 S202 C6 S202 C3 S202 C50 S202 C25 S202 C25 S202 C13 S202 C6 S202 C3
1000 Transformer 2CSM292873R0801 2CSM236913R0801 2CSM260093R0801 2CSM204413R0801
Fuse gauge 80 A 40 A 8 A 4 A 80 A 40 A 8 A 4 A
Breaker type S292 C80 S202 C40 S202 C8 S202 C4 S292 C80 S202 C40 S202 C8 S202 C4
1600 Transformer 2CSM292863R0801 2CSM201813R0801 2CSM260083R0801 2CSM204403R0801
Fuse gauge 125 A 63 A 16 A 8 A 125 A 63 A 16 A 8 A
Breaker type S292 C125 S202 C63 S202 C16 S202 C8 S292 C125 S202 C63 S202 C16 S202 C8
2000 Transformer 2CSM292853R0801 2CSM236903R0801 2CSM260073R0801 2CSM204383R0801
Fuse gauge 160 A 80 A 16 A 8 A 160 A 80 A 16 A 8 A
Breaker type - S292 C80 S202 C20 S202 C10 - S292 C80 S202 C20 S202 C10
2500 Transformer 2CSM236943R0801 2CSM207173R0801 2CSM204663R0801 2CSM204363R0801
Fuse gauge 200 A 100 A 20 A 10 A 200 A 100 A 20 A 10 A
Breaker type - S292 C100 S202 C25 S202 C13 - S292 C100 S202 C25 S202 C13
FUSES
- Gauge ≤ 6.3 A use aM fuses with high breaking capacity and IEC601266-compliant
- Gauge > 6.3 A use gG fuses IEC60269-2 or IEC60269-3-compliant
b TM-S 50/24-48 P complies with IEC EN 61558-2-4 on the secondary circuit at 48 V and with IEC EN 61558-2-6 on the secondary circuit at 24 V