 Technical features
 A41      A42                                A43                                 A44
 Voltage/current inputs
 Nominal voltage  230 V AC                   3x230/400 V AC
 Voltage range  57.7 - 288 V AC (-20% - +15%)  57.7 - 288 or 100 ... 288 V AC (-20% - +15%)  3x57.7/100 ... 288/500 V AC (-20% - +15%)  3x57.7/100 ... 288/500 or
                                                                                3x100/173 ... 400/690 V AC (-20% - +15%)
 Power dissipation voltage circuits  1.5 VA (0.6 W) total at 230 V AC  1.8 VA (0.8 W) total at 230 V AC
 Power dissipation current circuits  0.006 VA (0.006 W) at I  and I  0.001 VA (0.001 W) at I  and I  0.006 VA (0.006 W) per phase at I  0.001 VA (0.001 W) at I  and I *
 ref  b                  ref  n                                    ref                         ref  n
 Base current I b  5 A  -                    5 A                                -
 Rated current I  -  1 A                     -                                  1 A
 n
 Reference current I ref  5 A  1 A           5 A                                1 A
 Transitional current I  0.5 A  0.05 A       0.5 A                              0.05 A
 tr                                                                                                                    8
 Maximum current I  80 A  6 A                80 A                               6 A
 max
 Minimum current I min  0.25 A  0.02 A       0.25 A                             0.01 A
 Starting current I  < 20 mA  < 1 mA         < 20 mA                            < 1 mA
 st
 Terminal wire area  1 - 25 mm 2  0.5 - 10 mm 2  1 - 25 mm 2                    0.5 - 10 mm 2
 Recommended tightening torque  2 Nm  1.2 Nm  2 Nm                              1.2 Nm
 Communication
 Terminal wire area  0.5 - 1 mm 2                                         0.5 - 1 mm 2
 Recommended tightening torque  0.25 Nm                                    0.25 Nm
 Transformer ratios
 Configurable current ratio (CT)  -  1/9 - 9999/1  -                            1/9 - 9999/1
 Configurable voltage ratio (VT)  -  1/999 - 999999/1  -                        1/999 - 999999/1
 Pulse indicator (LED)
 Pulse frequency  1000 imp/kWh  5000 imp/kWh  1000 imp/kWh                      5000 imp/kWh
 Pulse length  40 ms  40 ms
 Frequency  50 or 60 Hz  ± 5%  50 or 60 Hz ± 5 % (or 16.7 Hz optional)  50 or 60 Hz ± 5 %
 Accuracy Class  B (Cl.1) and Reactive Cl. 2  B (Cl.1), C (Cl. 0,5 S) and Reactive Cl. 2  A (Cl.2), B (Cl.1) and Reactive Cl. 2  B (Cl.1), C (Cl. 0,5 S) and Reactive Cl. 2
 Active energy  1%  0.5%, 1%                 1%                                 0.5%, 1%
 Display of energy  Pixel oriented display (LCD)
 Environmental
 Operating temperature  -40°C - +70°C  -40°C - +70°C
 Storage temperature  -40°C - +85°C  -40°C - +85°C
 Humidity  75% yearly average, 95% on 30 days/year  75% yearly average, 95% on 30 days/year
 Resistance to fire and heat  Terminal 960°C, cover 650°C (IEC 60695-2-1)  Terminal 960°C, cover 650°C (IEC 60695-2-1)
 Resistance to water and dust  IP20 on terminal block without protective   IP20 on terminal block without protective enclosure and IP51 in protective enclosure, according to IEC 60529.
 enclosure and IP51 in protective enclosure,
 according to IEC 60529.
 Mechanical environment  Class M2 in accordance with the Measuring   Class M2 in accordance with the Measuring Instrument Directive (MID). (2014/32/EU).
 Instrument Directive (MID). (2014/32/EU).
 Electromagnetic environment  Class E2 in accordance with the Measuring   Class E2 in accordance with the Measuring Instrument Directive (MID), (2014/32/EU).
 Instrument Directive (MID), (2014/32/EU).








 *) For 690 V AC meters:
 Power dissipation voltage circuits 2.2 VA (1.0 W) total at 230 V AC
 Power dissipation current circuits 0.001 VA (0.001 W) per phase at Iref and In