Page 852 - Din prodcuts 2020
P. 852
9/22 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
SMISSLINE TP plug-in system
RCCBs F400 series, A APR y type
F402…K F404…K F404…S F404…B
Rated voltage U : 230 V 230/400 V 230/400 V 230/400 V
n
Number of poles: 2 4 4 4
Rated frequency f : 45 … 60 Hz 45 … 60 Hz 45 … 60 Hz 45 … 60 Hz
n
Resistance to surge 3 kA 3 kA 5 kA 1000 A
current: 8/20 µs 8/20 µs 8/20 µs ≤ 300 ms
≥ 40 ms
Total trip time
F402 (average value)
– at I∆n 240 ms 120 … 300 ms 150 … 500 ms
– at 5 I∆n ≤ 40 ms 40 …150 ms
Delay time at 5 I∆n: 10 ms 10 ms 90 ms
Resistance to short 10 kA 10 kA 10 kA 10,000 electrical
circuits (kA): in conjunction with operating cycles
an upstream fuse gL
/ gG 100 A 20,000 mechanical
or or a high operating cycles
9
performance MCB
S800 100 A
Connection Double lift terminal touch finger-proof, suitable for connecting
load side terminal single-, multi- and fine-wire conductors of up to 25 mm 2
Degree of protection: IP20 in panel IP40 IP20 in panel IP40 IP20 in panel IP40 IP20 in panel IP40
Endurance: > 5000 operating > 5000 operating > 5000 operating
cycles cycles cycles
Resistance to climate EN 61008 EN 61008 EN 61008 EN 62423
acc. to:
Mounting position: any any any any
Ambient –25°C … +40°C –25°C … +55°C –25°C … +40°C –25°C … +40°C
temperature:
Vibration resistance: 5 g 5 g 5 g 5 g
5 … 150 … 5 Hz 5 … 150 … 5 Hz 5 … 150 … 5 Hz 5 … 150 … 5 Hz
Plastic parts: halogen-free halogen-free halogen-free halogen-free
Contacts: cadmium-free cadmium-free cadmium-free cadmium-free