Page 15 - IDEC timer catalogue
P. 15
Timers GT3A Series
GT3A Series — Analog Timers
Key features of the GT3A series include:
• 4 selectable operation modes on each model
• External start, reset, and pause inputs
• Panel mount or socket mount Switches & Pilot Lights
• Large variety of timing functions
• Power and output status indicating LEDs
UL, c-UL Listed
File No. E55996
Specifi cations Display Lights
GT3A-1 GT3A-2 GT3A-3 GT3A-4,-5,-6
Operation Multi-mode Multi-mode with inputs (11 pins)
Time Range 0.1s to 180 hours
100 to 240V AC, 50/60Hz
Rated Voltage 12V DC
24V AC, 50/60Hz / 24V DC
125V AC/250V AC, 3A; 125V AC/250V AC, 5A;
Contact Ratings
30V DC, 1A (resistive load) 30V DC, 5A (resistive load)
Minimum Applicable Load 5V, 10mA (reference value)
AF20 (100V AC): 85 to 264V AC Relays & Sockets
Voltage Tolerance AD24: 20.4 to 26.4V AC/21.6 to 26.4V DC
D12: 10.8 to 13.2V DC
Error ±0.2%, ±10 msec (repeat, voltage, temperature)
Setting Error ±10% maximum
Reset Time 60msec maximum
Insulation Resistance 100MW minimum
Between power and output terminals: 2,000V AC, 1 minute
Dielectric Strength Between contacts of different poles: 2,000V AC, 1 minute
Between contacts of the same pole: 750V AC, 1 minute Timers
Delayed SPDT +
Delayed SPDT Delayed DPDT Delayed DPDT
instantaneous SPDT
10.8VA 13.5VA 14.4VA 4.7VA (100V AC, 60Hz),
Power Consumption (200V AC, 60Hz) (200V AC, 60Hz) (200V AC, 60Hz) 14.4VA (200V AC, 60Hz)
(approximate)
12VDC/1W 12VDC/1.1W 12VDC/0.8W
— 24VDC/0.7W 24VDC/0.6W 24VDC/0.6W
24VAC/1.2VA 24VAC/1.3VA 24VAC/1.3VA
Mechanical Life 10,000,000 operations minimum 5,000,000 operations minimum
Electrical LIfe 50,000 operations minimum (rated load) 100,000 operations minimum (rated load)
Weight (approximate) 63g 73g 79g 80g Terminal Blocks
Vibration Resistance 100m/sec (approximate 10G)
2
Operating extremes: 100m/sec (approximate 10G)
2
Shock Resistance
Damage limits: 500m/sec (approximate 50G)
2
Operating Temperature –10 to +50°C
Operating Humidity 45 to 85% RH
Storage Temperature –30 to +80°C
Housing Color Gray Circuit Breakers
USA: 800-262-IDEC Canada: 888-317-IDEC 805