Page 11 - IDEC timer catalogue
P. 11

Timers                                                                             RTE Series


                                                  Timing Diagrams con’t

                                                         RTE-P2, -B2



                      RTE-P2            RTE-B2                                                                         Switches & Pilot Lights
                   external
                   control  start   external
                   signal           control  start               1. RTE-P2: Do not apply voltage to terminals #5, #6 & #7.
                                    signal
                                                                 2. RTE-B2: Do not apply voltage to terminals #2, #5 & #8.
                         6             1  2  3
                       5  7
                      4    8                                     3. IDEC sockets are as follows: RTE-P2: SR3P-05* pin type socket,
                                       4  5  6
                      3     9                                      RTE-B2: SR3B-05* blade type socket, (*-may be followed by suffi x
                                        7  8  9
                       2   10                                      letter A,B,C or U).
                        1  11          A     B
                   (~/+)    (~/-)        (~/+)  (~/-)
        A: ON-Delay 2 (signal start)                           B: Cycle 2 (signal start, OFF fi rst)
        When a preset time has elapsed after the start input turned on while power is on, the NO output   When the start input turns on while power is on, the output oscillates at a preset cycle (duty ratio 1:1),
        contact goes on.                                       starting while the NO contact off.
          Item  Terminal Number         Operation                Item  Terminal Number         Operation               Display Lights
              (A) 2 - 10                                             (A) 2 - 10
         Power                                                  Power
              (B) A - B                                              (B) A - B
              (A) 5 - 6                                              (A) 5 - 6
         Start                                                  Start
              (B) 2 - 5                                              (B) 2 - 5
              (A) 1 - 4, 8 - 11  (NC)                                (A) 1 - 4, 8 - 11  (NC)
         Delayed   (B) 1 - 7, 3 - 9                             Delayed   (B) 1 - 7, 3 - 9
         Contact  (A) 1 - 3, 9 - 11                             Contact  (A) 1 - 3, 9 - 11
              (B) 4 - 7, 6 - 9  (NO)                                 (B) 4 - 7, 6 - 9  (NO)
              PWR                                                    PWR
         Indicator                                              Indicator
              OUT                                                    OUT
         Set Time                                               Set Time
                                      T                                             T  T  T  T  T  T  T  T  T  Ta

        C: Cycle 4 (signal start, ON fi rst)                    D: Signal ON/OFF-Delay                                  Relays & Sockets
        When the start input turns on while power is on, the NO contact goes on. The output oscillates at a   When the start input turns on while power is on, the NO output contact goes on. When a preset time
        preset cycle (duty ratio 1:1).                         has elapsed while the start input remains on, the output contact goes off. When the start input turns
          Item  Terminal Number         Operation              off, the NO contact goes on again. When a preset time has elapsed after the start input turned off, the
              (A) 2 - 10                                       NO contact goes off.
         Power
              (B) A - B
                                                                 Item  Terminal Number         Operation
              (A) 5 - 6
         Start                                                       (A) 2 - 10
              (B) 2 - 5                                         Power  (B) A - B
              (A) 1 - 4, 8 - 11  (NC)                                (A) 5 - 6
         Delayed   (B) 1 - 7, 3 - 9                             Start  (B) 2 - 5
         Contact  (A) 1 - 3, 9 - 11                                  (A) 1 - 4, 8 - 11
              (B) 4 - 7, 6 - 9  (NO)                                       (NC)
                                                                Delayed   (B) 1 - 7, 3 - 9
              PWR                                               Contact  (A) 1 - 3, 9 - 11  (NO)
         Indicator                                                   (B) 4 - 7, 6 - 9
              OUT                                                    PWR                                               Timers
                                                                Indicator
         Set Time                                                    OUT
                               T   T  T  T  T  T  T  T  Ta
        E: Signal OFF-Delay                                     Set Time           T     T        Ta  T    T    Ta
        When power is turned on while the start input is on, the NO output contact goes on. When a preset
        time has elapsed after the start input turned off, the NO output contact goes off.   F: One-Shot (signal start)
          Item  Terminal Number         Operation              When the start input turns on while power is on, the NO output contact goes on. When a preset time
              (A) 2 - 10                                       has elapsed, the NO output contact goes off.
         Power
              (B) A - B
                                                                 Item  Terminal Number         Operation
              (A) 5 - 6
         Start                                                       (A) 2 - 10
              (B) 2 - 5                                         Power
                                                                     (B) A - B
              (A) 1 - 4, 8 - 11  (NC)                                (A) 5 - 6
         Delayed   (B) 1 - 7, 3 - 9                             Start  (B) 2 - 5
         Contact  (A) 1 - 3, 9 - 11                                  (A) 1 - 4, 8 - 11
              (B) 4 - 7, 6 - 9  (NO)                                 (B) 1 - 7, 3 - 9  (NC)                            Terminal Blocks
                                                                Delayed
              PWR                                               Contact  (A) 1 - 3, 9 - 11  (NO)
         Indicator                                                   (B) 4 - 7, 6 - 9
              OUT                                                    PWR
                                                                Indicator
         Set Time
                              T           Ta    T      Ta            OUT
                                                                Set Time                                                Circuit Breakers
                                            USA: 800-262-IDEC          Canada: 888-317-IDEC                        801
   6   7   8   9   10   11   12   13   14   15   16