Page 44 - IDEC timer catalogue
P. 44
GT3W Series Timers
GT3W Series — Dual Time Range Timers
Switches & Pilot Lights Key features of the GT3W series include:
Sequential start, sequential interval, on-delay, recycler,
•
and interval ON timing functions
•
2 time settings in one timer
•
8 selectable operation modes on each model
•
Power and output status indicating LEDs
• Mountable in sockets or fl ush panel
• Time ranges up to 300 hours
UL, c-UL Listed
File No. E55996
Display Lights General Specifications Contact Ratings
Operation System
Operation Type Solid state CMOS Circuit Allowable Contact Power 960VA/120W
Allowable Voltage
Multi-Mode
250V AC/150V DC
Time Range 1: 0.1sec to 6 hours, 3: 0.1sec to 300 hours Allowable Current 5A
Pollution Degree 2 (IE60664-1) Maximum permissible 1800 cycles per hour
operating frequency
Over Voltage Category III (IE60664-1)
1/8HP, 240V AC
AF20 100-240V AC(50/60Hz) Rated Load 3A, 240V AC (Resistive)
Relays & Sockets AF20 12V DC Conditional Short Circuit 5A, 120V AC/30V DC
Rated Operational Voltage
24V AC(50/60Hz)/24V DC
AD24
D12
(Resistive)
85-264V AC(50/60Hz)
Fuse 5A, 250V
Voltage Tolerance
20.4-26.4V AC(50/60Hz)/21.6-26.4V DC
AD24
Electrical 100,000 op. minimum
D12 10.8-13.2V DC Life (Resistive)
Disengaging Value of Input Voltage Rated Voltage x10% minimum Mechanical 20,000,000 op. minimum
Range of Ambient Operating Temperature -10 to +50ºC (without freezing)
Range of Ambient Storage -30 to +75ºC (without freezing)
and Transport Temperature
Timers Range of Relative Humidity 35 to 85%RH (without condensation)
Atmospheric Pressure
80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport)
Reset Time 60msec maximum
Repeat Error ±0.2%, ±10msec*
Voltage Error ±0.2%, ±10msec*
Temperature Error ±0.6%, ±10msec*
Setting Error ±10% maximum
Insulation Resistance 100MΩ minimum (500V DC)
Terminal Blocks Dielectric Strength Between contacts of different poles: 2000V AC, 1 minute
Between power and output terminals: 2000V AC, 1 minute
Between contacts of the same pole:750V AC, 1 minute
2
Vibration Resistance
10 to 55Hz amplitude 0.75mm hours in each of 3 axes
2
Operating extremes: 98m/sec (approx.10G)
Shock Resistance Damage limits: 490m/sec (approx. 50G)
2
3 times in each of 3 axes
Degree of Protection IP40 (enclosure), IP20 (socket) (IEC60529)
100V AC/60Hz 2.3VA
Power Consumption AF20 200V AC/60Hz 4.6VA
Circuit Breakers Mounting Position AD24 (AC/DC) 1.8VA/0.9W
(Approx.)
Free
Dimensions
72g
Weight (Approx.) 40Hx 36W x 70 mm
* For the value of the error against a preset time, whichever the largest applies.
834 www.idec.com