GT3F Series                                                                          Timers


                                                 Instructions: Wiring Inputs

     Switches & Pilot Lights  To avoid electric shock, do not touch the input signal terminal during power voltage application.
        Inputs of GT3F

        Never apply the input signals to two or more GT3F timers using the same contact or transistor.
        [Incorrect]
                  GT3 Series
        Input
                  Timer
        Contact or Transistor
                   Terminal
                                               Terminal
                2  Input  10  Power  [correct]  2  Input  10  Power
                   Input                       Input
                   Terminal                    Terminal
                2     10                         2  10
        In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
     Display Lights  GT3 Series  Power
                   Timer
                    Input
                    Terminal
                      Rectifier
                Circuit  Circuit
                Insulating Transformer
        On the GT3F timers, connect the input signals to terminal No.1 and 4 only on the 8-pin type; connect the input signals to terminal No. 6 and 7 only on the 11-pin type.
     Relays & Sockets  ing.
        Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
        Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for input wir-

        The GT3F, consisting of a high-impedance circuit, may not be reset due to the infl uence of an inductive voltage or residual voltage caused by a leakage current. If not
        reset, connect an RC fi lter or bleeder resistor between power terminals so that the voltage between power terminals can be reduced to less than 15% of the rated
        voltage.