Page 40 - IDEC timer catalogue
P. 40
GT3F Series Timers
Instructions: Wiring Inputs
Switches & Pilot Lights To avoid electric shock, do not touch the input signal terminal during power voltage application.
Inputs of GT3F
Never apply the input signals to two or more GT3F timers using the same contact or transistor.
[Incorrect]
GT3 Series
Input
Timer
Contact or Transistor
Terminal
Terminal
2 Input 10 Power [correct] 2 Input 10 Power
Input Input
Terminal Terminal
2 10 2 10
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
Display Lights GT3 Series Power
Timer
Input
Terminal
Rectifier
Circuit Circuit
Insulating Transformer
On the GT3F timers, connect the input signals to terminal No.1 and 4 only on the 8-pin type; connect the input signals to terminal No. 6 and 7 only on the 11-pin type.
Relays & Sockets ing.
Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for input wir-
The GT3F, consisting of a high-impedance circuit, may not be reset due to the infl uence of an inductive voltage or residual voltage caused by a leakage current. If not
reset, connect an RC fi lter or bleeder resistor between power terminals so that the voltage between power terminals can be reduced to less than 15% of the rated
voltage.
Timers
Terminal Blocks
Circuit Breakers
830 www.idec.com