Page 42 - IDEC timer catalogue
P. 42
GT3S Series Timers
General Specifications Solid state CMOS circuitry
Operation System
Switches & Pilot Lights Operation Type Star-delta
Star side: 0.05 to 100 sec
Time Range
Star-delta switching time:
0.05, 0.1, 0.25, 0.5 sec
Rated Operational Voltage
Operating Temperature 100 to 240V AC (50/60Hz)
-10 to +50˚C
Storage Temperature -30 to +80˚C
Operating Humidity 45 to 85% RH
Voltage Tolerance 85 to 264V AC
Display Lights Repeat Error ±0.2%, ±10 msec
±0.2%, ±10 msec
Voltage Error
Temperature Error
±10% maximum
Setting Error ±0.2%, ±10 msec
Reset Time 500 msec maximum
Insulation Resistance 100MΩ minimum
Between power and output terminals: 2,000V AC, 1 minute
Dielectric Strength Between contacts of different poles: 2,000V AC, 1 minute
Relays & Sockets Vibration Resistance 100 m/sec (Approx. 10G) 2 2
Between contacts of the same pole: 750V AC, 1 minute
2
Operating extremes: 100m/sec (Approx. 10G)
Shock Resistance
Damage limits: 500m/sec (Approx. 50G)
Power Type 2.3VA (100V AC, 60Hz),
GT3S-1
4.0VA (200V AC, 60Hz)
Consumption
(Approx.) Type 2.3VA (100V AC, 60Hz),
GT3S-2 3.8VA (200V AC, 60Hz)
Timers
Terminal Blocks
Circuit Breakers
832 www.idec.com