Page 45 - OTDC Switch
P. 45
OTDC M-SERIES 45
—
Ordering information, IEC and UL
OTDC M-Series 250…1000A for higher short-circuit current
Robust DC switch-disconnector for up to 1500V DC applications covering 315-1000A (IEC) and 250-1000A
(UL) current range. The new design offers higher short-circuit ratings for the OTDC switches up to 100kA.
Handles and shafts are not included.
— 05
IEC Ordering information
— Rated operational
OTDC315_630_F_11-ESS current [A] Number Number of Single package
Voltage [V DC] DC-21B DC-PV2 of circuits Circuit 1) poles Type Order code
Front operated, mechanism between the poles
1000 315 315 1 2a, 2b 2 OTDC315F11-ESS 1SCA158173R1001
1000 400 400 1 2a, 2b 2 OTDC400F11-ESS 1SCA158197R1001
1000 500 500 1 2a, 2b 2 OTDC500F11-ESS 1SCA158221R1001
1000 630 500 1 2a, 2b 2 OTDC630F11-ESS 1SCA158245R1001
1000 800 - 1 6c, 6g 4 OTDC800F22-ESS 1SCA161279R1001
1000 1000 - 1 6c, 6g 4 OTDC1000F22-ESS 1SCA161287R1001
1500 315 315 1 2a, 2b 2 OTDC315FV11-ESS 1SCA158179R1001
1500 400 400 1 2a, 2b 2 OTDC400FV11-ESS 1SCA158203R1001
1500 500 500 1 2a, 2b 2 OTDC500FV11-ESS 1SCA158227R1001
1500 630 500 1 2a, 2b 2 OTDC630FV11-ESS 1SCA158251R1001
1500 800 - 1 6c, 6g 4 OTDC800FV22-ESS 1SCA161281R1001
1500 1000 - 1 6c, 6g 4 OTDC1000FV22-ESS 1SCA161289R1001
—
UL Ordering information
Rated operational
current [A] Single package
Voltage [V Number Number of
DC] UL98B IEC60947-3 of circuits Circuit 1) poles Type Order code
Front operated, mechanism between the poles
1000 250 315 1 2a, 2b 2 OTDC250UF11-ESS 1SCA158161R1001
1000 320 400 1 2a, 2b 2 OTDC320UF11-ESS 1SCA158185R1001
1000 400 500 1 2a, 2b 2 OTDC400UF11-ESS 1SCA158210R1001
1000 600 630 1 2a, 2b 2 OTDC600UF11-ESS 1SCA158234R1001
1000 800 800 1 6c, 6g 4 OTDC800UF22-ESS 1SCA161283R1001
1000 1000 1000 1 6c, 6g 4 OTDC1000UF22-ESS 1SCA161291R1001
1500 250 315 1 2a, 2b 2 OTDC250UFV11-ESS 1SCA158167R1001
1500 320 400 1 2a, 2b 2 OTDC320UFV11-ESS 1SCA158191R1001
1500 400 500 1 2a, 2b 2 OTDC400UFV11-ESS 1SCA158216R1001
1500 600 630 1 2a, 2b 2 OTDC600UFV11-ESS 1SCA158240R1001
1500 800 800 1 6c, 6g 4 OTDC800UFV22-ESS 1SCA161285R1001
1500 1000 1000 1 6c, 6g 4 OTDC1000UFV22-ESS 1SCA161293R1001
1) Circuit connection 6c, 6g – connection bar kit OTDCKIT800FS11 included with the package – installation mandatory.
Please see floating circuit in page 46 and the grounded circuits in pages 56-57. Single circuit 1a and Double circuit 3 with connection bar kit
accessories.
You can find the accessories starting from page 47 and dimensional drawings starting from page 61.