40               SWITCH-DISCONNECTORS OTDC AND OTDCP




          —
          Technical data
          OTDC M-Series UL




          —
          Technical data in accordance to UL98B for photovoltaic disconnect switches OTDC250U_…1000UF_
          Suitable for use in photovoltaic systems in accordance with article 690 of the NEC.
          Switch size                             OTDC250UF_ OTDC320UF_ OTDC400UF_ OTDC600UF_ OTDC800UF_22 OTDC1000UF_22
          UL Listed    Standard                   UL98B    UL98B     UL98B     UL98B     UL98B       UL98B
          Rated ambient temperature            °C -20…+50  -20…+50   -20…+50   -20…+50   -20…+50     -20…+50
          Rated current  1)  1000V   1 circuit  2P (1P+, 1P-)  A  250  320  400  600     800  2)     1000  2)
                              2 circuits 4P (2P+, 2P-)  A  250  320  400       600       -           -
                       1500V   1 circuit  2P (1P+, 1P-)  A  250  320  400      600       800  2)     1000  2)
                              2 circuits 4P (2P+, 2P-)  A  250  320  400       600       -           -
          Short circuit rating  1500V          kA 10       10        10        10        10          10
          Required                                Any      Any       Any       Any       Any         Any
          protection  3)
          Mechanical lug                          OZXA 402  OZXA 402  OZXA 402  OZXA 604  OZXA 804   OZXA 804
          Wire range                              2x AWG   2x AWG    2x AWG    4x AWG    4x AWG      4x AWG
                                                  6-300MCM  6-300MCM  6-300MCM  6-300MCM  2-600MCM   2-600MCM
          Tightening torque                    lb- 275     275       275       275       500         500
                                               in.
          Technical data   See IEC table for type  OTDC315F_  OTDC400F_  OTDC500F_  OTDC630F_  OTDC800F_22  OTDC1000F_22
          according to IEC
          60947
          1)  For more detailed derating please consult us. Installation condition may influence on the derating. The given deratings are references based on specific test setup.
          2)   4-pole-types with 2-poles in parallel _22 models, OTDCKIT800FS11 is included to the package and installation is mandatory.
          3)  Any suitable PV fuse or PV circuit breaker.











                         —                                              —
                         OTDC250...600UF_11                             OTDC800...1000UF_22