ACCESSORIES 6/5
Signalling
Open / closed auxiliary contacts - AUX (Fig. 01A/B/C)
SACE Emax 2 circuit-breakers can be equipped with auxiliary contacts that signal the open or closed
status of the circuit-breaker. The first block of four standard contacts is always provided with the auto-
matic circuit-breakers. The switching contacts are available in the following configurations:
Open / closed auxiliary contacts (AUX 4Q) E1.2 E2.2 … E6.2
4 auxiliary standard
contacts digital signals
— mixed
Fig. 01-A
Open / closed supplementary auxiliary contacts (AUX 6Q)
6 auxiliary standard -
contacts digital signals -
mixed -
Open / closed external supplementary auxiliary contacts (AUX 15Q)
15 auxiliary standard
contacts digital signals
—
Fig. 01-B Maximum number of open / closed 19 25
auxiliary contacts that can be installed
Standard contact Contact for digital signals
Type changeover contacts changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
DC 24V - 0.1A 06
125V 0.3A @ 10ms -
250V 0.15A @ 10ms -
AC 250V 5A @ cosϕ 1 -
—
Fig. 01-C 5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -
—
Electrical diagram reference: figures 1, 81, 91
Aux 6Q is an alternative to the Ekip Signalling 4K module. AUX 15Q is an alternative to the mechanical
interlock (MI), the DLC for E1.2 lock or the DLP lock if mounted on the right side.