6/6              SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS



          —

          Accessories for circuit-breakers






                           Auxiliary position contacts - AUP (Fig. 02A/B)
                           When the circuit-breaker is a withdrawable version, the position of the mobile part can be signalled
                           electrically by accessorizing the fixed part with one of the following signalling contact units:
                           Auxiliary position contacts (AUP)   E1.2                    E2.2 … E6.2
                           6 auxiliary   standard                                      -
                           contacts   digital signals                                  -
                           5 auxiliary   standard              -
                           contacts   digital signals          -
                           5          standard                 -
                           supplementary
          —                auxiliary
          Fig. 02-A                   digital signals          -
                           contacts
                           Maximum number of auxiliary position   6                    10
                           contacts that can be installed

                                                               Standard contact        Contact for digital signals
                           Type                                changeover contacts     changeover contacts
                           Minimum load                        100mA @ 24V             1mA @ 5V
                           Breaking capacity
          —
          Fig. 02-B        DC         24V                      -                       0.1A
                                      125V                     0.3A @ 0ms              -
                                      250V                     0.15A @ 0ms             -
                           AC         250V                     5A @ cosϕ 1             -
                                                               5A @ cosϕ 0.7           -
                                                               5A @ cosϕ 0.3           -
                                      400V                     3A @ cosϕ 1             -
                                                               2A @ cosϕ 0.7           -
                                                               1A @ cosϕ 0.3           -
                           —
                           Electrical diagram reference: figures 95, 96, 97

                           Ready to close signalling contact - RTC (Fig. 03)
                           The ready to close signalling contact – RTC – indicates that the circuit-breaker is ready to receive the closing
                           command. The circuit-breaker is ready to close when the following conditions have been met:
                           •  circuit-breaker open
                           •  springs loaded
                           •  no opening command or locks on the opening command
                           •  circuit-breaker reset following tripping of Ekip protection trip unit
                           •  YU energized.
                                                               Standard contact        Contact for digital signals
                           Type                                Switching
                           Minimum load                        100mA @ 24V             1mA @ 5V
                           Breaking capacity
                                      24V                      -                       0.1
          —                DC
          Fig. 03                     250V                     0.5A @ 0ms / 0.2A 10ms  -
                           AC         250V                     3A @ cosϕ 0.7           -
                           —
                           Electrical diagram reference: figure 71