6/6 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS
—
Accessories for circuit-breakers
Auxiliary position contacts - AUP (Fig. 02A/B)
When the circuit-breaker is a withdrawable version, the position of the mobile part can be signalled
electrically by accessorizing the fixed part with one of the following signalling contact units:
Auxiliary position contacts (AUP) E1.2 E2.2 … E6.2
6 auxiliary standard -
contacts digital signals -
5 auxiliary standard -
contacts digital signals -
5 standard -
supplementary
— auxiliary
Fig. 02-A digital signals -
contacts
Maximum number of auxiliary position 6 10
contacts that can be installed
Standard contact Contact for digital signals
Type changeover contacts changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
—
Fig. 02-B DC 24V - 0.1A
125V 0.3A @ 0ms -
250V 0.15A @ 0ms -
AC 250V 5A @ cosϕ 1 -
5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -
—
Electrical diagram reference: figures 95, 96, 97
Ready to close signalling contact - RTC (Fig. 03)
The ready to close signalling contact – RTC – indicates that the circuit-breaker is ready to receive the closing
command. The circuit-breaker is ready to close when the following conditions have been met:
• circuit-breaker open
• springs loaded
• no opening command or locks on the opening command
• circuit-breaker reset following tripping of Ekip protection trip unit
• YU energized.
Standard contact Contact for digital signals
Type Switching
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
24V - 0.1
— DC
Fig. 03 250V 0.5A @ 0ms / 0.2A 10ms -
AC 250V 3A @ cosϕ 0.7 -
—
Electrical diagram reference: figure 71