Page 119 - Sace Emax 2 Catalogue
P. 119

ACCESSORIES                                                                      6/17














                           The mechanical interlocks offer multiple solu-  ATS022 is also designed for the connection of an
                           tions for installation that simplify their integra-  auxiliary supply, which enables the use of further
                           tion into the switchgear. The interlocks can be   functions.
                           mounted:                                    The ATS021 and ATS022 devices carry out control
                           •  vertically VR                            of both power supply lines and also analyze:
                           •  horizontally HR                          •  phase imbalance;
                           •  mixed L                                  •  frequency imbalance;
                                                                       •  phase loss.
                           Different types of interlocks can be supplied ac-  In addition to the standard control functions, the
                           cording to the maximum distance between two   ATS022 unit also permits:
                           interlocked breakers:                       •  the priority line to be selected;
                           Configuration       Type A    Type B, C, D  •  a third circuit-breaker to be controlled;
                                                                       •  the device to be integrated into a supervision
                           Horizontal          2750mm    1600mm
                                                                        system with Modbus communication (auxiliary
                           Vertical            1000mm    1000mm         supply needed);
                           Breakers  E1.2                -             •  parameters to be read and set, and measure-
                                    E2.2
                                                                        ments and alarms to be displayed by means of a
                                    E4.2                                graphical display.
                                    E6.2
                                                                       Typical applications are: supply of UPS (Uninter-
                           For B, C and D types, the maximum distance be-  rupted Power Supply) units, operating rooms and
                           tween the two furthest breakers is 3200mm for   primary hospital services, emergency power for
                           horizontal configurations and 2000mm for verti-  civil buildings, airports, hotels, databases and
                           cal configurations. It is possible to make the me-  telecommunication systems and power supply of   06
                           chanical interlock among three circuit-breakers   industrial lines in continuous processes.
                           disposed in 'L position' by using the cables of   For correct configuration, each circuit-breaker
                           three horizontal circuit-breakers interlock. Make   connected to the ATS021 or ATS022 device must
                           sure the distance between the horizontal and ver-  be fitted with the following accessories:
                           tical circuit-breakers respects the minimum and   •  mechanical interlock;
                           maximum distance. All cables can be cut to guar-  •  motorized control of opening and closing;
                           antee easy installation in switchboards.    •  contact for signalling status (open / closed) and
                           Mechanical interlocks are not compatible with AUX   contact for signalling tripping;
                           15Q, the lock for preventing door opening when   •  contact for signalling circuit-breaker racked in
                           the circuit breaker is in the closed position (DLC)   (for withdrawable circuit-breaker).
                           or when the circuit breaker is in the racked in or
                           test position (DLP). if mounted on the right side.

                           External Automatic Transfer Switches ATS
                           The ATS (Automatic Transfer Switch) is a net-
                           work-unit transfer device used in installations
                           where switching from the main power line to an
                           emergency line is required in order to ensure that
                           power is supplied to the loads in the case of
                           power loss or abnormalities from the main line.
                           These devices are able to control the entire trans-
                           fer procedure automatically, but also offer com-
                           mands for performing the procedure manually.
                           The new generation of ATSs (ATS021 and ATS022)
                           offers the most advanced and complete solution
                           for ensuring service continuity. The ATS021 and
                           ATS022 devices can also be used with all auto-
                           matic circuit-breakers and switch-disconnectors
                           of the Tmax XT family. The ATS021 and ATS022 de-
                           vices have been designed to be self-powered.