Page 123 - Sace Emax 2 Catalogue
P. 123

ACCESSORIES                                                                      6/21














                           Power supply
                           Ekip Supply module (Fig. 23)
                           The Ekip Supply module supplies all Ekip trip units and modules present on the terminal box
                           and of the circuit-breaker with several auxiliary power (in AC or DC) available in the switchgear.
                           The module is mounted in the terminal box and permits the installation of the other advanced
                           modules. It can be field installed at any time.
                           Two versions are available according to the control voltage available:
                           •  Ekip Supply 110-240V AC/DC
                           •  Ekip Supply 24-48V DC

                                          Supply                     Ekip Supply
          —                Ekip Dip       Nominal voltage           24-48V DC             110-240V AC/DC
          Fig. 23
                                          Voltage range             21,5-53V DC           105-265V AC/DC
                                          Rated power (including modules)  10W max.       10W max.
                                          Inrush current            ~2A for 20ms          ~2A for 20ms
                           Ekip Touch/    Nominal voltage           24-48V DC             110-240V AC/DC
                           Hi-Touch       Voltage range             21,5-53V DC           105-265V AC/DC
                                          Rated power (including modules)  10W max.       10W max.
                                          Inrush current            ~2A for 20ms          ~2A for 20ms

                           Connectivity
                           Ekip Com modules (Fig. 24)
                           The Ekip communication modules enable SACE Emax 2 circuit-breakers to be integrated in an industrial   06
                           communication network for remote supervision and control of the circuit-breaker. They are suitable for
                           all distribution and generator protection versions of the Ekip Touch and Hi-Touch trip units. Since they
                           are mounted in the terminal box, communication can be maintained with withdrawable circuit-breakers,
                           even while in the racked-out position. Several Ekip Com modules can be installed at the same time,
                           thereby enabling connection to communication systems that use different protocols.
                           The Ekip Com modules for Modbus RTU, Profibus-DP and DeviceNet™ contain a terminating resistor
                           and dip switch for optional activation to terminate the serial network or bus.
                           The Profibus-DP module also contains a polarization resistor and dip switch for its activation.
                           The Ekip Com modules are supplied with auxiliary position contacts Ekip AUP and
          —                ready to close circuit-breaker contacts Ekip RTC.
          Fig. 24
                           For industrial applications in which a higher reliability of the communication network is required, the
                           Ekip Com Redundant modules can be installed together with the corresponding Ekip Com modules in
                           order to guarantee a back-up connection to the network.

                           The following communication protocols are available for Ekip trip units:

                           Protocol             Ekip Com Module                 Ekip Com Redundant Module
                           Modbus RTU           Ekip Com Modbus RS-485          Ekip Com R Modbus RS-485
                           Modbus TCP           Ekip Com Modbus TCP             Ekip com R Modbus TCP
                           Profibus-DP          Ekip Com Profibus               Ekip Com R Profibus
                           Profinet             Ekip Com Profinet               Ekip Com R Profinet
                           EtherNet/IP™         Ekip Com EtherNet/IP™           Ekip Com R EtherNet/IP™
                           DeviceNet™           Ekip Com DeviceNet™             Ekip Com R DeviceNet™
                           IEC61850             Ekip Com IEC61850               Ekip Com R IEC61850
                           Cloud connectivity   Ekip Com Hub                    –
                           —
                           Electrical diagram reference: figures from 51 to 57. Redundant version from 61 to 66.
   118   119   120   121   122   123   124   125   126   127   128