Page 120 - Sace Emax 2 Catalogue
P. 120
6/18 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS
—
Accessories for circuit-breakers
Technical characteristics
ATS021 ATS022
General Auxiliary supply voltage Not required Not required
(24-110V DC is required only for
Modbus communication and
systems of 16 2/3 Hz)
Supply voltage, Un Max 480V AC Max 480V AC
Frequency, fn 50, 60 Hz 16 2/3, 50, 60, 400 Hz
Dimensions H mm 96 96
H W mm 144 144
W D D mm 170 170
Type of installation Installation on front of switchgear Installation on front of
Installation switchgear Installation
on DIN rail on DIN rail
Operating mode Automatic/Manual Automatic/Manual
Characteristics Monitoring of normal and emergency line
Control of circuit-breakers on normal and emergency line
Setting start-up of generator
Setting switch-off of generator with settable time delay
Third circuit-breaker -
Selection priority line -
Modbus Rs485 communication -
Display -
Environmental Protection degree IP20* IP20*
conditions Operating temperature -20 … +60 °C -20 … +60 °C
Humidity 5% - 90% without condensation 5% - 90% without condensation
Operating Undervoltage -30% … -5% Un -30% … -5% Un
thresholds
Overvoltage +5% …+30% Un +5% …+30% Un
Frequency thresholds -10% / +10% fn -10% … +10% fn
Tests Test Mode
Mode Test Gen set
Standards Electronic devices for use in electrical installations EN-IEC 50178 EN-IEC 50178
Electromagnetic compatibility EN 50081-2 EN 50081-2
EN 50082-2 EN 50082-2
Environmental conditions IEC 68-2-1 IEC 68-2-1
IEC 68-2-2 IEC 68-2-2
IEC 68-2-3 IEC 68-2-3
Electrical diagram reference: figures 100,101 and 102.
* IP54 available with 1SCA101001R1001 accessory