Page 139 - Sace Emax 2 Catalogue
P. 139

INSTALL ATION                                                                     7/5














                           Poles                                       are available with neutral set at 50 percent of nor-
                           SACE Emax 2 circuit breakers are available in three-  mal supply and with full-sized neutral, so that the
                           pole and four-pole versions and can be used in all   customer does not need to oversize the neutral
                           types of distribution systems. Furthermore, with   unless strictly necessary.
                           the possibility of connecting the external current          L1  L2   L3
                           sensor, three-pole circuit breakers can be used ef-  The standard supplied circuit breakers are suitable
                           ficiently even in systems in which the neutral con-  for connection of phases in the sequence L1, L2, L3
                           ductor cannot be isolated.                  for three-pole circuitbreakers, or N, L1, L2 and L3
                                                                       for four-pole circuit breakers with neutral on the
                           The four-pole circuit breakers E1.2, E2.2 and E4.2   left; a special optional kit enables the position of
                           are always provided with full-size neutral pole with   the circuit breaker neutral to be changed to the
                           rated uninterrupted current-carrying capacity   L1  L2 right, making the sequence L1, L2, L3, N available
                                                                                                L3
                                                                                           L2
                                                                                       L1
                                                                                   N
                                                                          L3
                           identical to the phase poles. The E6.2 circuit-   (refer to page 9/53 for the commercial codes).
                           breakers, thanks to their construction modularity,
 Withdrawable
                           Circuit-breaker   Standard version                    Optional version with neutral on the right
                                          Three-pole       Four-pole             Four-pole
                           Emax E1.2       L1   L2  L3       N   L1   L2  L3      L1   L2  L3   N

                           Emax E2.2

                           Emax E4.2
                           Emax E6.2
                                       N   L1   L2  L3
                                                             L1  L2   L3  N



                                                                                                                       07



                                       L1  L2   L3   N
   134   135   136   137   138   139   140   141   142   143   144