7/8 SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS
—
Circuit-breaker
Temperature derating carrying capacity at the reference temperature:
Under certain installation conditions, the circuit- therefore the derating coefficients shown in the
breakers can operate at higher temperatures than table must be applied. Percentage values refer to
the reference temperature of 40 °C. In this case withdrawable and fixed circuit breaker.
the current-carrying capacity of the circuit- If not specified, all data refer to a copper accord-
breaker may be lower than the rated current- ing to IEC60947.
Emax 2 E1.2 Cross section Temperature [°C]
<40 45 50 55 60 65 70
E1.2 250 100% 100% 100% 100% 100% 100% 100%
E1.2 630 100% 100% 100% 100% 100% 100% 100%
E1.2 800 100% 100% 100% 100% 100% 100% 100%
E1.2 1000 100% 100% 100% 100% 100% 100% 100%
E1.2 1250 100% 100% 100% 100% 100% 100% 100%
E1.2 1600 100% 100% 100% 98% 95% 93% 90%
E1.2 1600 1200 mm 2 100% 100% 100% 100% 97% 95% 92%
Emax 2 E2.2 Cross section Temperature [°C]
<40 45 50 55 60 65 70
E2.2 250 100% 100% 100% 100% 100% 100% 100%
E2.2 800 100% 100% 100% 100% 100% 100% 100%
E2.2 1000 100% 100% 100% 100% 100% 100% 100%
E2.2 1250 100% 100% 100% 100% 100% 100% 100%
E2.2 1600 100% 100% 100% 100% 100% 100% 98%
E2.2 2000 100% 100% 100% 100% 95% 91% 87%
E2.2 2500 100% 100% 100% 100% 98% 94% 90%
Emax 2 E4.2 Cross section Temperature [°C]
<40 45 50 55 60 65 70
E4.2 2000 100% 100% 100% 100% 100% 100% 100%
E4.2 2500 100% 100% 100% 100% 100% 100% 100%
E4.2 3200 3000 mm 2 100% 100% 97% 93% 89% 86% 82%
E4.2 3200 3000 mm 2 100% 100% 100% 100% 95% 93% 89%
(*)
E4.2 4000 4000 mm 2 100% 100% 97% 93% 89% 86% 83%
(*) Three stabs terminal kit only for withdrawable version
Emax 2 E6.2 Cross section Temperature [°C]
<40 45 50 55 60 65 70
E6.2 4000 4000 mm 2 100% 100% 100% 100% 100% 100% 100%
E6.2 5000 5000 mm 2 100% 100% 100% 100% 100% 98% 95%
E6.2 6300 6000 mm 2 100% 100% 95% 91% 87% 84% 81%