Page 20 - Sace Emax 2 Catalogue
P. 20

2/6              SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          SACE Emax 2/E9 circuit breakers up to 900V








          ABB SACE Emax 2/E9 circuit breakers can effectively and simply control all wind
          and solar applications - with the highest availability and continuity of service.


                           The world of renewable energy is evolving rapidly   Emax 2/E9 all-in-one is the first smart circuit
                           causing major changes in electrical power distri-  breaker that enables  direct communication with
                           bution trends. This causes an increased focus on:   the new energy management cloud-computing
                           •  Power continuity for critical loads and the best   platform ABB Ability™ Energy and Asset Manager.
                            performance, even at high altitudes        Smart and plug-and-play architecture makes
                           •  Optimized, fast maintenance              Emax 2/E9 all-in-one easy to use.
                           •  Minimized device footprint               With the best performance up to 900 V of any
                                                                       device on the market, Emax 2/E9 is ready to con-
                           These trends lead to new customer and applica-  trol and protect all applications with voltages
                           tion demands. To meet these demands, ABB has   over 690 V.
                           now unveiled the innovative Emax 2/E9 all-in-one,
                           the evolution of the Emax 2 into a multifunctional   Emax 2/E9 sets a new circuit-breaker benchmark
                           platform that is able to manage the next genera-  for the electrical power distribution systems of
                           tion of electrical plants such as microgrids.  today and tomorrow.


          Common data
          Rated service voltage Ue        [V]    900
          Rated insulation voltage Ui     [V]    1000
          Rated impulse withstand voltage Uimp  [kV]  12
          Frequency                       [Hz]   50 - 60
          Number of poles                        3- 4
          Version                                Fixed - Withdrawable
          Suitable for isolation according to    IEC 60947-2


          SACE Emax 2/E9                                     E1.2   E2.2           E4.2           E6.2
          Performance levels                                 N/E9   S/E9    H/E9    S/E9   H/E9   H/E9   X/E9
          Rated uninterrupted current Iu @ 40°C        [A]   1250   1250    1250    3200   3200   5000   5000
                                                       [A]          2000    2000    4000   4000   6300   6300
                                                       [A]          2500    2500
         Neutral pole current-carrying capacity for 4-pole CBs  [%Iu]  100  100  100  100  100    50-100  50-100
         Rated ultimate short-circuit breaking capacity Icu  800V  [kA]  35  50  65  65    90     90     100
                                               900V    [kA]         50      65      65     75     75     90
         Rated service short-circuit breaking capacity Ics  [%Icu]  100  100  100   100    100    100    100
         Rated short-time withstand current Icw  (1s) 800V  [kA]  35  50    65      65     75     75     90
                                               (3s) 800V  [kA]  30  50      65      65     75*    75     90
                                               (1s) 900V  [kA]      50      65      65     75     75     90
                                               (3s) 900V  [kA]      50      65      65     75*    75     90
         Rated short-circuit making capacity (peak value) Icm  800V  [kA]  73.5  105  143  143  200  200  220
                                               900V    [kA]         105     143     143    165    165    198
         Utilization category (according to IEC 60947-2)     B      B       B       B      B      B      B

         SACE Emax 2/E9                           E1.2**     E2.2             E4.2             E6.2
                                    [Iu]          <1000 1250  <2000 2000  < 2500 <3200 3200  4000  4000  5000  6300
         Mechanical life*           [No. cycles x 1000] 20  20  25  25  20    20    20   15    12    12   12
                        Frequency   [Oper./Hour]  60   60    60    60   60    60    60   60    60    60   60
         Electrical life  900 V     [No. cycles x 1000] 0,5  0,5  2  2  2     1     1    1     1     1    1
                        Frequency   [Oper./Hour]  30   30    30    30   30    10    10   10    10    10   10
          *with regular ordinary maintenance prescribed by the manufacturer. ** For E1.2, electrical life is at 800V.
   15   16   17   18   19   20   21   22   23   24   25