Page 21 - Sace Emax 2 Catalogue
P. 21

THE R ANGES                                                                   2/7



          —

          SACE Emax 2 derived versions


                                                                                                                       02




          Safety is an indispensable requirement that must always be
          guaranteed in electrical installations. In this regard, ABB SACE offers
          devices developed to further increase safety standards during
          inspection and maintenance activities on electrical installations.

          In particular, in a withdrawable version, ABB SACE Emax 2 offers:


          —                                                            •  Sectionalizing truck CS: in normal operating
          The earthing circuit
          is dimensioned for a                                          conditions of the electrical circuit, this device is
          short-time current equal                                      inserted in the part. It short-circuits the upper
          to 60% of the maximum
          Icw of the circuit breaker                                    and lower terminals of the power circuit. When
          from which it is                                              maintenance activities need to be carried out,
          derived (IEC 60439-1)
                                                                        the sectionalizing truck is removed and the part
                                                                        of the system involved is isolated. The device
                                                                        can be accessorized with a keylock and pad-
                                                                        locks for locking in the withdrawn position.




          —                                                            •  Earthing truck MT: this device enables all phases
          The standard fixed parts
          can not accept MT/MTP                                         of the electrical circuit on which maintenance
          device. In order to allow                                     needs to be performed to be earthed  .
                                                                                                      1)
          the utilization of MT/MTP
          mobile parts is mandatory                                     The earthing truck is available in two versions:
          to install the grounding                                      for earth connection from the upper or lower
          clamps on fixed parts.
          Accessorizing only                                            terminals.
          in the factory.
   16   17   18   19   20   21   22   23   24   25   26