2/8              SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          SACE Emax 2 derived versions













                                                                       •  Earthing switch with making capacity MTP:
                                                                        similar to the MT device, this differs due to the
                                                                        presence of a mechanical stored energy control
                                                                        which allows the circuit to be opened and
                                                                        closed. Two versions of this earthing switch are
                                                                        also available: for earth connection from the up-
                                                                        per or lower terminals. It can also be acces-
                                                                        sorized
                                                                       •   with a keylock or padlocks for locking in the
                                                                        open position.























         Common data
         Rated service voltage Ue         [V]    690
         Rated insulation voltage Ui      [V]    1000
         Rated impulse withstand voltage Uimp  [kV]  12
         Frequency                        [Hz]   50 - 60
         Number of poles                         3 - 4
         Version                                 Withdrawable

         SACE Emax 2                             E2.2                 E4.2                 E6.2
         Performance levels                      CS     MT     MTP    CS     MT     MTP    CS     MT     MTP
         Rated uninterrupted current  Iu @ 40°C  2500   2500   2500   4000   4000   4000   6300   6300   6300
         Neutral pole current-carrying capacity for 4-pole CBs  100  100  100  100  100  100  50-100  50-100  50-100
         Rated short-time withstand current Icw (1s) [kA]   -  30  30  -     50     50     -      50     50
   17   18   19   20   21   22   23   24   25   26   27