Page 200 - Sace Emax 2 Catalogue
P. 200
8/42 SACE EMAX 2 LOW VOLTAGE AIR CIRCUIT-BREAKERS
—
Withdrawable circuit-breaker - E6.2
Flat terminals
E6.2 H/V/X 4000...6300A
—
Key
1 Flat terminal
2 Tightening torque on
power circuit
connections 45Nm
3 Door position -
Ref. page 7/20
4 Grounding
7 Mounting fixed part
screws provided
M8x25 head convex
high class 8.8 or
couple superior
Tightening torque
20Nm compulsory
fixing from high
8 Moving part
9 Fixed part
10 Segregation
(when provided)
11 Connected, test,
disconnected
distances
13 Metallic sheet